Inter-Circuit Fault Location Algorithm for Two-Parallel Transmission Line

Inter-Circuit Fault Location Algorithm for Two-Parallel Transmission Line
下载PDF
导出
摘要 A novel numerical algorithm of fault location estimation for four-line fault without ground connection involving phases from each of the parallel lines is presented in this paper. It is based on one-terminal voltage and current data. The loop and nodal equations comparing faulted phase to non-faulted phase of two-parallel lines are introduced in the fault location estimation model, in which the source impedance of a remote end is not involved. The effects of load flow and fault resistance on the accuracy of fault location are effectively eliminated, therefore a precise algorithm of locating fault is derived. The algorithm is demonstrated by digital computer simulations. A novel numerical algorithm of fault location estimation for four-line fault without ground connection involving phases from each of the parallel lines is presented in this paper. It is based on one-terminal voltage and current data. The loop and nodal equations comparing faulted phase to non-faulted phase of two-parallel lines are introduced in the fault location estimation model, in which the source impedance of a remote end is not involved. The effects of load flow and fault resistance on the accuracy of fault location are effectively eliminated, therefore a precise algorithm of locating fault is derived. The algorithm is demonstrated by digital computer simulations.
出处 《Transactions of Tianjin University》 EI CAS 2003年第3期189-192,共4页 天津大学学报(英文版)
基金 SupportedbyKeyScienceFoundationofTianjin(No .0 2 380 1 2 1 1 )
关键词 内部电路故障定位算法 并行传输线 输电线路故障 电路理论 fault location estimation two-parallel line four-line fault
  • 相关文献

参考文献9

  • 1Zamore I;Minambres J F;Mazon A J.Fault location on two-terminal transmission lines based on voltages,1996(01).
  • 2Novosel D;Hart D G;Udren E.Unsynchronized two-terminal fault location estimation[J],1996(01).
  • 3Kezunovic M;PERUNICIC B.Automated transmission line fault analysis using synchronized sampling at two end,1996(01).
  • 4Zhang Qingchao;ZHANG Yao;SONG Wennan.Transmission line fault location for phase-to-earth using one-terminal data,1999(02).
  • 5Zhang Qingchao;Zhang Yao;Song Wennan.Fault location of two-parallel transmission line for non-earth fault using one-terminal data[J],1999(03).
  • 6Djuric M B;Radojevic Z M;Terzija V V.Time domain solution of fault distance estimation and arcing faults detection on overhead lines[J],1999(01).
  • 7Djuric M B;Radojevic Z M;Terzija V V.Distance protection and fault location utilizing only phase current phasors[J],1998(04).
  • 8Eriksson L;SAHA M M;ROCKFELLER G D.An accurate fault location with compensation for apparent reactance in the fault resistance resulting from remote-end infeed,1985(02).
  • 9Kezunovic M;Perunicic B.Synchronized sampling improves fault location[J],1995(01).