期刊文献+

SF_6气体水分管理标准的探讨及密度与湿度监测的研究 被引量:20

DISCUSSION ABOUT THE WATER VAPOR CONTENT STANDARD & RESEARCH ON MONITORING SF_6 GAS'S DENSITY AND HUMIDITY
下载PDF
导出
摘要 该文对国内外SF6气体水分控制标准进行了认真的分析,提出采用气体实时相对湿度(RH%)来保证SF6电气设备的安全可靠运行。为了在温度变化很大的情况下使离线监测的数据具备可比较性,修正到20℃时的绝对水气压不失为一个比较好的控制参数。针对目前因为水分受温度影响造成的监测难点,指出采用在线监测方法对SF6气体进行监测具有很大的优势。并用实验室数据曲线验证了对气体在线监测的可行性。 The State and IEEE standards for SF6 gas抯 Moisture Measurement and Control are analyzed and oppugned in this paper. We present that limiting relative humidity(RH%) can ensure the GIE(Gas-insulated equipment) against danger. In order to make the data measured offline at various temperaturecomparable, the absolute pressure of water vapor, which ismeasured at any temperature, should be calculated to that of 20℃.At present, the difficulty of measurement and control is the effects of temperature. Because moisture is absorbed on allsolid surfaces in the system or absorbed in the solid insulator material. The gas online monitoring method has a lot ofadvantage. The feasibility of online monitoring is validated by experiment.
机构地区 华中科技大学
出处 《中国电机工程学报》 EI CSCD 北大核心 2003年第10期169-174,共6页 Proceedings of the CSEE
关键词 电气设备 六氟化硫气体 微水含量 水分管理标准 密度 湿度监测 High voltage equipment SF6 gas Water vapor content Density
  • 相关文献

参考文献7

二级参考文献13

  • 1陆夕云,庄礼贤,童秉纲.对称TVD差分格式的构造及其应用[J].计算物理,1994,11(1):45-50. 被引量:2
  • 2徐黎明.压气式SF6高压断路器开断性能仿真分析和智能操作:博士学位论文[M].西安:西安交通大学,1998..
  • 3苏方春.超高压断路器智能操作自适应控制单元的研究:硕士学位论文[M].西安:西安交通大学,1998..
  • 4陈晓宁,高电压技术,1998年,24卷,4期
  • 5徐黎明,博士学位论文,1998年
  • 6苏方春,硕士学位论文,1998年
  • 7Zhang X,Proc 2nd Int Conf Electrical Contacts Arcs Apparatus and Their Applications,1993年,79页
  • 8国际电工委员会,国际电工辞典.开关设备、控制设备和熔断器,1989年
  • 9陈慈萱,高压电器,1987年
  • 10蔡庆东,计算物理,1998年,15卷,4期,476页

共引文献50

同被引文献204

引证文献20

二级引证文献179

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部