IDC机房UPS系统案例分析 被引量:2

The Case Analysis of UPS System in IDC Computer Room
下载PDF
导出
摘要 以某通信运营商新建IDC机房UPS系统为例,详细介绍了机房近期及远期负荷的估算方法,分析了目前大楼高低压供电现状,最后针对估算出的近期、远期的通信负荷,提出了合理的UPS系统建设方案,解决了通信负荷供电。同时详细介绍了UPS系统配电设备的使用及选型,其中包括配电柜、ATS、UPS主机、后备蓄电池组,为方案的具体实施提供了可靠依据。 The estimation methods of computer room short and long term load was introduced in detail by taking a telecommunications operator new IDC room UPS system as an example.The status quo of building high and low voltage power supply was also analyzed and finally the reasonable UPS system construction scheme to estimate the short-term and longterm communication load was put forward.This can solve the communication load power supply.At the same time,the use and selection of UPS system power distribution equipment are introduced in detail,including the distribution cabinet,ATS,UPS host and backup battery,which provide a reliable basis for the specific implementation of the program.
作者 吴静 丁加军
出处 《通信电源技术》 2016年第5期140-143,共4页 Telecom Power Technology
关键词 IDC机房 UPS供电系统设计 配电设备 IDC computer room system design of UPS power supply power distribution equipment
  • 相关文献

参考文献1

二级参考文献10

  • 1YD/T5040-2005,通信电源设备安装工程设计规范[S].
  • 2GB50343-2004.建筑物电子信息系统防雷技术规范[S].[S].,..
  • 3GB50052-1995.供配电系统设计规范[S].,..
  • 4JGJ 16-2008 民用建筑电气设计规范[S].
  • 5GB5W52--95.供配电系统设计规范[S].中国:中华人民共和国机械工业部,1996.
  • 6YD/T5098-2005.通信局(站)防雷与接地工程设计规范[S].
  • 7信文.信息产业部发布七项通信行业标准[J].信息安全与通信保密,2003(03):8.
  • 8吴坤君,雷宏江,李强.通信电源设备的可靠性分析[J].通信技术,2008,41(3):126-128. 被引量:21
  • 9冯海,孙哲,陈文,孙权.可持续运营通信机楼建设的思考[J].通信技术,2010,43(6):77-79. 被引量:3
  • 10李峰.数据中心供配电系统设计[J].通信技术,2010,43(6):227-231. 被引量:14

共引文献3

同被引文献10

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部