基于双点检测SRAPF的环形配电系统背景谐波衰减策略研究

RESEARCH ON HARMONIC MITIGATING BASED ON DOUBLE POINT DETECTION OF SINGLE RESISTIVE ACTIVE POWER FILTER IN CLOSED-LOOP DISTRIBUTION SYSEMS
下载PDF
导出
摘要 对于环型配电网,具有较高的供电可靠性,已然成为一种发展趋势,其线路电感与功率因数校正电容之间的谐振使得系统背景谐波电压谐振放大,导致电力系统中的谐波电压严重畸变。针对环形配电网中谐波谐振现象,提出一种基于双点检测单阻性有源滤波器(double point detection of single resistive active power filter,DPDSRAPF)的谐波衰减策略,即检测环形配电网中2个节点(其中一个节点为中点,另一节点为中点以外的节点)的谐波电压,而APF和非线性负载改变等工况下,具有更好的鲁棒性和谐波衰减效果。仿真分析和实验结果均验证该方案的正确性和有效性。 As a kind of development trend,the closed-loop distribution feeder has high power supply reliability. The harmonic resonance caused by capacitors for power factor correction and system inductors may lead to significant voltage distortion along the feeder. For this phenomenon,this paper proposes an double point detection of single resistive active power filter(DPDSRAPF)to damp out the harmonic resonance. The principle of the strategy is that the harmonic voltage of two nodes(one of the nodes is the midpoint,another node is outside the midpoint)are tested and APF is only installed at the middle point of the closed-loop distribution feeder. The proposed strategy has better capability of harmonic damping and harmonic mitigating,especially in response to variation of line impedance and non-linear loads. Both simulation and experiment results have been provided to validate the proposed strategy.
作者 沈虹 李雪苗 康佳 孙孝峰 Shen Hong;Li Xuemiao;Kang Jia;Sun Xiaofeng(Key Lab of Power Electronics for Energy Conservation&Motor Drive of Hebei Province,College of Electrical Engineering,Yanshan University,Qinhuangdao 066004,China)
出处 《太阳能学报》 EI CAS CSCD 北大核心 2019年第2期572-579,共8页 Acta Energiae Solaris Sinica
基金 国家自然科学基金(51407155) 河北省自然科学基金(E2016203156)
关键词 双点检测单阻性有源滤波器 环形配电网 谐波谐振 谐波衰减 DPDSRAPF closed-loop distribution feeder harmonic resonance harmonic mitigation
  • 相关文献

参考文献6

二级参考文献78

  • 1肖湘宁,侯维宁.电力系统谐波统计分析与测量[J].华北电力学院学报,1993(3):37-44. 被引量:3
  • 2葛少云,张国良,申刚,刘孚智,张祖荣.中压配电网各种接线模式的最优分段[J].电网技术,2006,30(4):87-91. 被引量:56
  • 3王广柱.有源电力滤波器两种补偿目标的分析和比较[J].中国电机工程学报,2007,27(19):115-120. 被引量:8
  • 4何英杰,邹云屏,刘飞,黄柱.高压大容量有源电力滤波器并联运行研究[J].电工技术学报,2007,22(6):94-100. 被引量:22
  • 5刘进军,刘波,王兆安.基于瞬时无功功率理论的串联混合型单相电力有源滤波器[J].中国电机工程学报,1997,17(1):37-41. 被引量:85
  • 6Wada K, Fujita H, Akagi H. Consideration of a shunt active filter based on voltage detection for installation on a long distribution feeder[J]. IEEE Transactions on Industry Applications, 2002, 38(4): 1123-1129.
  • 7Zhuo Fang, Wu Longhui, Chen Zhe. Study on a control method of PAPF for resonance damping and harmonices compensation in power system[C]//Proceedings of International Power Electronics and Motion Control Conference. Wuhan: IEEEPEL, 2009: 1161-1167.
  • 8Pogaku N, Green T C. Harmonic mitigation throughout a distribution system a distributed generator based solution [J]. IEE Proceedings: Generation Transmission and Distribution, 2006, 153(3): 150.
  • 9Akagi H. Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems[J]. IEEE Transactions on Power Delivery, 1997, 12(1): 354-363.
  • 10Wada K, Fujita H, Akagi H. Considerations of a shunt active filter based on voltage detection for installation on a long distribution feeder[J]. IEEE Transactions on Industry Applications, 2002, 38(4): 1123-1130.

共引文献61

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部