摘要 差动保护是电力变压器的主保护,但变压器空载合闸时出现的励磁涌流易造成差动保护误动作,如果能准确鉴别励磁涌流和故障电流,就能提高保护动作的可靠性。本文在二次谐波制动原理的基础上,提出了一种基于电压突变量的励磁涌流辅助判据,并利用MATLAB软件对励磁涌流进行仿真。 Differential protection is Lord of the power transformer protection,but there was a excitation inrush current of transformer no-load closing easy to cause the differential protection misoperation,if can accurately identify excitation inrush current and fault current,it can improve the reliability of protection action.Based on second harmonic braking principle,is proposed based on a voltage mutation of excitation inrush current auxiliary criterion,and excitation inrush current to make use of MATLAB software simulation.
出处 《电子测试》 2013年第4X期52-53,共2页 Electronic Test
关键词 变压器差动保护 励磁涌流 二次谐波制动 电压突变量 Transformer differential protection excitation inrush current Second harmonic brake voltage mutation