期刊文献+

含电缆出线变电站内短路电流分流系数仿真分析 被引量:6

Analysis of Affecting Factors on Fault Shunt Coefficient in Substation with Cable Outlets
下载PDF
导出
摘要 变电站内发生短路故障时,真正会对变电站造成危害的是通过变电站地网入地的电流,因此研究短路电流的分流系数有重要意义。电力电缆结构与架空线不同,二者的分流系数存在较大的差别。基于PSCAD软件,仿真计算了含电缆出线的变电站发生短路的地网分流系数,探讨了电缆长度、交叉互联等因素对分流系数的影响。计算结果表明,当变电站出线为电缆线路时,发生短路时地网分流系数远小于架空线路,减小了对变电站地网的分流要求,但同时也会导致短路电流增大,两者应当综合考虑。 While a short-circuit fault occurs in a substation,it's the current diffused into ground that actually causes the safeness trouble and hence it's important to study the fault shunt coefficient.The structure of cables is different from that of the overhead lines so that the shunt coefficient is distinct.This paper adopts PSCAD to calculate the fault shunt coefficient in the substation with cable outlets,and analyzes the influencing factors including the length of the cables,cross-bonding etc.The results show that the fault shunt coefficient of the substations with cable outlets is far lower than that of substations only with overhead lines,and therefore the requirement for the shunt capability of grounding grids is reduced.But at the same time,it will cause larger short-circuit current,so overall consideration is needed.
出处 《陕西电力》 2016年第7期1-5,69,共6页 Shanxi Electric Power
基金 国家自然科学基金资助项目(51277107)
关键词 短路电流 分流系数 电缆 接地 变电站 线路 short-circuit fault shunt coefficient cable grounding substation line
  • 相关文献

参考文献27

  • 1许继葵,牛海清,王晓兵,张尧.高压电缆网络短路分流系数的研究[J].高电压技术,2007,33(10):142-146. 被引量:8
  • 2文习山,胡建平,唐炬.复杂电力网络短路电流分布及地网分流系数[J].高电压技术,2011,37(9):2233-2240. 被引量:36
  • 3Bo Zhang,Yukuan Jiang,Jinpeng Wu,He Jinliang et al.Influence of Potential Difference Within Large Grounding Grid on Fault Current Division Factor. IEEE Transactions on Power Delivery . 2014
  • 4ZHANG B,JIANG Y K,HE J L,et al.Experimental and Numerical Study of Division Factors of Fault Current and Measuring Current Due to Ground Wires of Transmission Lines. IEEE Transactions on Industry Applications . 2015
  • 5Ametani,A.A General Formulation of Impedance and Admittance of Cables. Power Apparatus and Systems, IEEE Transactions on . 1980
  • 6Lee, C.-H.,Chang, C.-N.Computation of current-division factors and assessment of earth-grid safety at 161/69 kV indoor-type and outdoor-type substations. Generation, Transmission and Distribution, IEE Proceedings- . 2005
  • 7IEEE guide for safety of AC substation groundings. ANSI/IEEE std 80—2000 . 2000
  • 8Roberto Benato,Sebastian Dambone Sessa,Fabio Guglielmi.Determination of Steady-State and Faulty Regimes of Overhead Lines by Means of Multiconductor Cell Analysis (MCA). ENERGIES . 2012
  • 9GB/T 50065-2011.交流电气装置的接地设计规范[S]. 2011
  • 10吴锦鹏,张波,蒋愉宽,曾嵘,何金良.基于相分量模型的变电站短路电流分流系数计算[J].中国电机工程学报,2012,32(1):122-130. 被引量:39

二级参考文献298

共引文献596

同被引文献53

引证文献6

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部