期刊文献+

低压双回路自投时间测试整定方法的研究

Testing and Adjusting Methods Research of Automatic Change over Time in the Low-Voltage Double-Loop Power Supply System
下载PDF
导出
摘要 针对一级负荷高可靠性的供电要求,提出了一种测试低压双回路供电系统自投时间的方法,并精确地测试了双回路自投时间。进而,根据断路器特性和设备对停电间隙的要求,对断路器自投时间进行了整定。 To counter the high reliability demand of class I load power supply, a method of test automatic change over time in the low voltage double-loop power. supply system has been put forward, at the same time, the automatic change over time of low voltage double-loop power supply system has been tested accurately. Moreover, based on the demand of conventional circuit breaker characteristic and equipment vs power cut time, the automatic change over time of conventional circuit breaker was adjusted.
出处 《低压电器》 2004年第1期44-47,共4页 Low Voltage Apparatus
关键词 供电系统 电力系统 可靠性 低压双回路 自投时间 测试 整定 low voltage double-loop power supply test adjustment
  • 相关文献

参考文献4

  • 1.GJB/Z 94—1997.军用电气系统安全设计手册[S].,..
  • 2.GB50174-1993.电子计算机机房设计规范[S].,..
  • 3焦留成.供电设计手册[M].北京:中国计划出版社,1999..
  • 4电气工程师第二版编辑委员会.电气工程师手册 [M].北京:机械工业出版社,2002..