期刊文献+

变电站接地电极的腐蚀与防护研究 被引量:12

Corrosion and Protection of Earth Screen in Transformer Substation
下载PDF
导出
摘要 为了研究变电站接地网在降阻剂中的腐蚀情况 ,用化学分析的方法测试了变电站的土壤和所用降阻剂的理化性质 ,用失重法分析了除去镀锌层后的A3钢电极在土壤和降阻剂中的腐蚀情况。试验结果表明 ,A3钢电极在弱碱性降阻剂中的腐蚀比在中性土壤中的腐蚀严重 ,主要原因是降阻剂中含有Cl-使降阻剂成为一种强腐蚀性介质 ,造成了电极的点蚀穿孔。通过动态恒电位扫描法测定A3钢在各种溶液中的极化曲线以获得各离子对电极的自腐蚀电位和孔蚀电位的影响 ,结果表明在降阻剂中加入缓蚀剂 ,如磷酸盐和硅酸盐 ,可以缓解降阻剂中Cl-对A3钢的点蚀影响 ,使降阻剂既能降低接地电阻又可缓解接地网的腐蚀。 To study the corrosion of grounding grids in transformer substation, the constitutes, pH and moisture of soil and reducing resistance reagent in transformer substation were measured by chemical analysis, and the pitting corrosion on A3 steel grounding electrodes scraped off zinc plating in reducing resistance reagent was observed in lab. Factors effecting corrosion behavior of grounding grids were investigated. Cl^- in the reducing resistance reagent is the key for the corrosion of earth screen. The pitting corrosion potential and corrosion potential of A3 steel electrode in soil containing of 4% NaCl move positively by adding some corrosion inhibitors such as NO^-_3, CO^(2-)_3, PO^(3-)_4, SiO^(2-)_3. Adding inhibitors as PO^(3-)_4 and SiO^(2-)_3 to the reducing resistance reagent can decrease the corrosion of earth screen.
出处 《材料保护》 CAS CSCD 北大核心 2004年第2期9-11,共3页 Materials Protection
关键词 变电站 接地电极 腐蚀 防护 孔蚀 A3钢 土壤 降阻剂 接地网 pitting corrosion A3 steel soil reducing resistance reagent
  • 相关文献

参考文献3

共引文献38

同被引文献98

引证文献12

二级引证文献83

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部