期刊文献+

基于小波变换的同杆并架双回线双端行波故障测距 被引量:44

WAVELET TRANSFORM BASED DOUBLE TERMINAL METHOD OF TRAVELLING WAVE FAULT LOCATION IN DOUBLE-CIRCUIT PARALLEL TRANSMISSION LINE
下载PDF
导出
摘要 利用小波变换的双端行波测距新方法,可有效提取同杆并架双回线路故障行波特征并消除行波色散对定位精度的影响,同时解决了如何定义行波到达时间和选取行波传播速度的问题。大量仿真测距结果证实论文方法的测距精度基本不受线路长度、故障位置、故障类型、接地电阻大小等的影响,测距精度能在一个挡距内,满足精确故障定位的要求。 A new double terminal method of travelling wave fault location using wavelet transform for double-circuit parallel transmission line is presented. It can effectively extract the characteristics of travelling waves and eliminate the effects of the travelling wave dispersion on the fault location accuracy. In addition, it makes the definition of arrival time and the choice of propagation velocity more reasonable. A large amount of simulation results show that the new method is accurate and reliable. The accuracy of the method is not affected by line length, fault positions, fault types, grounding resistance, and it can meet the requirements of advanced fault location.
出处 《电力系统自动化》 EI CSCD 北大核心 2004年第5期51-55,共5页 Automation of Electric Power Systems
基金 原国家电力公司重大科技项目资助项目(SP11-2001-01-03)。
关键词 故障测距 小波变换 行波 同杆并架双回线路 fault location wavelet transform travelling wave double-circuit parallel transmission line
  • 相关文献

参考文献5

二级参考文献16

  • 1崔锦泰 程正兴(译).小波分析导论[M].西安:西安交通大学出版社,1995..
  • 2徐丙垠 葛耀中 等.利用暂态电流行波的输电线路故障测距技术.第五届全国继电保护学术会议论文集[M].北京:中国电机工程学会继电保护专委会,1993.125-132.
  • 3覃剑.小波变换应用于输电线路行波故障测距的研究[M].北京:中国电力科学研究院,1998..
  • 4宗孔德,数字信号处理,1998年
  • 5杨福生,清华大学电机与应用电子技术系讲义,1996年
  • 6秦前清,实用小波分析,1994年
  • 7覃剑,小波变换应用于输电线路行波故障测距的研究 [D],1998年
  • 8程正兴(译),小波分析导论,1995年
  • 9秦前清,实用小波分析,1994年
  • 10徐丙垠,第五届全国继电保护学术会议论文集,1993年,125页

共引文献205

同被引文献279

引证文献44

二级引证文献625

相关作者