摘要
分析了放电线圈开口三角二次绕组的末端与连线的接触电阻严重不平衡的形成,得出了接触电阻严重不平衡是导致零序电压保护动作的原因。
The formation of the severe imbalance of contact resistance between the end of unclose delta on secondary discharge winding and connecting wire is analysed. Consequently the paper draws a conclusion that the severe imbalance of contact imbalance caused the maloperation of zero-sequence voltage protection.
出处
《继电器》
CSCD
北大核心
2004年第9期76-77,共2页
Relay
关键词
电力系统
零序电压保护
接触电阻
放电线圈
discharge winding
contact resistance
unclose delta
unbalanced voltage