逆流式过冷—高温水蓄冷空调系统特性实验研究 被引量:3

Experiment of dynamic performance of a counterflow supercooling and chilled water storage air conditioning system
下载PDF
导出
摘要 介绍了大过冷度制冷—高温水蓄冷空调系统的原理 ,成功调试了大过冷度制冷循环 ,在冷凝温度为 4 1.5℃、最大过冷度为 33.5℃时系统仍能正常运行 ,最大制冷量增加了 2 0 4 %。分析了过冷度与蓄冷水供冷量、制冷量增量的关系 。 Presents the principle of the system. Successfully adjusts the supercooling refrigeration system with the maximal supercooling degree up to 33.5 ℃ when condensation temperature is 41.5 ℃. The refrigeration capacity of new system increases 20.4% than conventional air conditioning systems. Analyses the relation of supercooling degree to cooling capacity of chilled water and refrigeration capacity increment. Discusses the dynamic property of refrigeration system and cooling storage system in supercooling refrigeration cycle.
出处 《暖通空调》 北大核心 2004年第5期7-13,共7页 Heating Ventilating & Air Conditioning
关键词 过冷 水蓄冷 蓄冷空调 空调系统 制冷量 supercooling, chilled water storage, cool storage air conditioning, dynamic performance
  • 相关文献

参考文献2

  • 1Chen Zeshao, Cheng Wenlong, Ito Takehiro.A new scheme of air conditioning with cold storage by water through the method of supercooling refrigerant.1997 China-Japan Joint Symposium on Advanced Energy and Transportation Engineering, Yellow Mountain City, China, 1997
  • 2方贵银.空调水蓄冷温度分层动态特性模拟[J].暖通空调,1999,29(6):11-13. 被引量:10

共引文献9

同被引文献21

引证文献3

二级引证文献5