摘要 用试验和理论分析了大型综合性酒店类建筑物主风口总风量(新风+排风)对该侧楼外噪声的影响.风量过大则该侧噪声超标,对主风口总风量的选定构成约束.试验证明主风口侧的总风量不超过550000m3/h(风口面积77m2),即约为全楼现行空调用总风量(新风+排风)的25%左右,可保证噪声不超标. The influence of the wind rate (fresh air rate and exhaust air rate) of the main air port on the noise spreading from inside to outside in large-scale all-around hotel was discussed. If the wind rate was excessive, the noise of this side would go beyond the standard rate, thus the amount of the fresh air should be restrained. To ensure the noise satisfy the needs of the standard rate, the total wind rate of the main air port, less than 550000 m3/h (S=77 m2) and about 25% of the total wind rate (fresh air rate and exhaust air rate) of the present whole-building air condition, was recommended.
出处 《大连理工大学学报》 EI CAS CSCD 北大核心 2004年第3期383-387,共5页 Journal of Dalian University of Technology
关键词 大型综合性酒店 主风口 噪声 建筑物 风量 Acoustic noise Architectural design Hotels Structural design Wind effects
  • 相关文献

参考文献6

  • 1OLESEN B W. International development of standards for ventilation of building [J]. ASHRAE J, 1997(4):31-39.
  • 2LAWSON C N. Ventilation where it came from, where it is, and where it is going [J]. ASHRAE Trans, 1995(11):58-59.
  • 3REESE J A. ASHRAE standard 62R:how it could affect segments of the air conditioning industry [J]. ASHARY J, 1997(1):30-36.
  • 4汪善国.新风量、新风和新回风系统及控制[J].暖通空调,1997,27(1):23-28. 被引量:17
  • 5马大酋.噪声控制学[M].北京:科学出版社,1987.32-33.
  • 6张重起.机电设备噪声控制学[M].北京:轻工业出版社,1989.78-84.