摘要
The control strategy for asynchronized turbogenerators (ASTGs) was studied by using two-axis equations. Simulation of the process of an asynchronized turbogenerator with faults of d or q axis or d and q axes in the excitation system was carried out with the simulating models including the model of the reverse thyristors in the excitation system established by Saber software. The simulation results show that at the loss of excitation at both windings or one winding of the rotor, the ASTGs can be automatically driven into an asynchronous or single axis excitation operation mode without a power unit tripping, and the characteristics for ASTGs with faults in the excitation system appear in good order.
The control strategy for asynchronized turbogenerators (ASTGs) was studied by using two-axis equations. Simulation of the process of an asynchronized turbogenerator with faults of d or q axis or d and q axes in the excitation system was carried out with the simulating models including the model of the reverse thyristors in the excitation system established by Saber software. The simulation results show that at the loss of excitation at both windings or one winding of the rotor, the ASTGs can be automatically driven into an asynchronous or single axis excitation operation mode without a power unit tripping, and the characteristics for ASTGs with faults in the excitation system appear in good order.