期刊文献+

基于EFPI传感器的SF<sub>6</sub>/N<sub>2</sub>混合气体GIS局放模式识别研究

Research on Partial Discharge Pattern Recognition of SF<sub>6</sub>/N<sub>2</sub> Mixed Gas GIS Based on EFPI Sensor
下载PDF
导出
摘要 非本征法布里帕罗干涉(Extrinsic Fabry-Perot Interferometer, EFPI)的光纤超声传感器具有灵敏度高、抗干扰能力强等优点,将其应用于以新型SF6/N2混合气体作为绝缘介质的GIS内部局部放电的模式识别中,这对于GIS绝缘状态评估具有重要意义。分别在充有0.4 MPa纯SF6气体、20% SF6/80% N2混合气体、纯N2气体的GIS腔体内设置了4种放电模型,在单次超声脉冲波形特征参数提取的基础上,利用支持向量机算法(Support Vector Machine, SVM)对局放超声信号进行了模式识别,三种绝缘气体环境下的识别正确率均能达到85%以上。由于SF6对超声波的强吸收效应,随着SF6气体浓度的升高,超声波的衰减更为严重,不同类型局部放电的识别正确率也随之降低。 Extrinsic Fabry-Perot interferometer (EFPI) optical fiber ultrasonic sensor has the advantages of high sensitivity and strong anti-interference ability. The application of it to the pattern recognition of partial discharge in the GIS with the new SF6/N2 mixed gas as the insulating medium is of great significance for the evaluation of the insulation state of the GIS. Four discharge models are set up in the GIS cavity filled with 0.4 MPa pure SF6 gas, 20% SF6/80% N2 mixed gas, and pure N2 gas respectively. Based on the extraction of the characteristic parameters of the single ultrasonic pulse waveform, support vector machine (SVM) was used to identify the partial discharge ultrasonic signal, and the recognition accuracy rate can reach 85% in three insulating gas environments. Due to the strong absorption effect of SF6 on ultrasonic waves, as the concentration of SF6 gas increases, the attenuation of ultrasonic waves becomes more serious, and the recognition accuracy of different types of partial discharges also decreases.
出处 《智能电网(汉斯)》 2021年第3期189-198,共10页 Smart Grid
  • 相关文献

参考文献10

二级参考文献168

  • 1孙才新,许高峰,唐炬,侍海军,朱伟.检测GIS局部放电的内置传感器的模型及性能研究[J].中国电机工程学报,2004,24(8):89-94. 被引量:80
  • 2罗日成,李卫国,李成榕,熊浩,畅广辉.基于改进PSO算法的变压器局部放电超声定位方法[J].电力系统自动化,2005,29(18):66-69. 被引量:32
  • 3肖登明,李旭光,秦松林.特高压输变电系统中GIS气体放电特性[J].高电压技术,2007,33(6):6-8. 被引量:19
  • 4赵雷,陈伟民,章鹏.光纤法布里-珀罗传感器光纤端面反射率优化[J].光子学报,2007,36(6):1008-1012. 被引量:8
  • 5Wang W, Wu Y K, Wang Z, et al. Method of Fabry-Perot fiber sensor in partial discharge detection[C]//2012 International Conference on Computer Distributed and Intelligent Environmental Monitoring. Los Alamitos, USA: IEEE, 2012: 407-410.
  • 6Tian Y, Lewin P L. Partial discharge on-line monitoring for HV cable systems using electrooptic modulators[J]. IEEE Transactions on Di- electrics and Electrical Insulation, 2004, 11(5): 861-869.
  • 7Wang X D, Li B Q, Roman H T, et al. Acousto-optical PD detection for transformers[J]. IEEE Transactions on Power Delivery, 2006, 21 (3): 1068-1073.
  • 8Wang X D, Li B Q, Xiao Z X, et al. An ultra-sensitive optical MEMS sensor for partial discharge detection[J]. Journal of Micromechanics and Microengineering, 2005, 15(3): 521-527.
  • 9Wang X D, Li B Q, Onofrio L, et al. Diaphragm design guidelines and an optical pressure sensor based on MEMS technique[J]. Microclee- tronics Journal, 2006, 37(1): 50-56.
  • 10Song J H, Lee S S. Fiber-optic acoustic transducer utilizing a dual-core collimator combined with a reflective micromirror[J], Microwave and Optical Technology Letters, 2006, 48(9): 1833-1836.

共引文献377