Analysis for the Defect of Chromatogram in 35kv Oil-immersed Electric Reactor

Analysis for the Defect of Chromatogram in 35kv Oil-immersed Electric Reactor
下载PDF
导出
摘要 A defect of chromatogram in a 35kV oil-immersed three-phase one-piece electric reactor in a 500kV substation。The initial analysis suggests that the defect is caused by the loose connection of the iron core magnet shield (magnet shield layer of iron core or earthling top). Examination of winding DC resistance, DGA and other relevant examinations were carried out to investigate the defect reasons., which is demonstrated by the dismantlement. In-depth study is taken and corresponding prevention measures are put forward in the paper. A defect of chromatogram in a 35kV oil-immersed three-phase one-piece electric reactor in a 500kV substation。The initial analysis suggests that the defect is caused by the loose connection of the iron core magnet shield (magnet shield layer of iron core or earthling top). Examination of winding DC resistance, DGA and other relevant examinations were carried out to investigate the defect reasons., which is demonstrated by the dismantlement. In-depth study is taken and corresponding prevention measures are put forward in the paper.
出处 《Energy and Power Engineering》 2013年第4期838-841,共4页 能源与动力工程(英文)
关键词 OIL-IMMERSED Electric REACTOR Chromatogram DEFECT MAGNET SHIELD Layer Partial DISCHARGE Oil-immersed Electric Reactor Chromatogram Defect Magnet Shield Layer Partial Discharge