Experimental Study on the Cyclic Ampacity and Its Factor of 10 kV XLPE Cable 被引量:1

Experimental Study on the Cyclic Ampacity and Its Factor of 10 kV XLPE Cable
下载PDF
导出
摘要 The load varies periodically, but the peak current of power cable is controlled by its continuous ampacity in China, resulting in the highest conductor temperature is much lower than90℃, the permitted long-term working temperature of XLPE. If the cable load is controlled by its cyclic ampacity, the cable transmission capacity could be used sufficiently. To study the 10 kV XLPE cable cyclic ampacity and its factor, a three-core cable cyclic ampacity calculation software is developed and the cyclic ampacity experiments of direct buried cable are undertaken in this paper. Experiments and research shows that the software calculation is correct and the circuit numbers and daily load factor have an important impact on the cyclic ampacity factor. The cyclic ampacity factor of 0.7 daily load factor is 1.20, which means the peak current is the 1.2 times of continuous ampacity. If the continuous ampacity is instead by the cyclic ampacity to control the cable load, the transmission capacity of the cable can be improved greatly without additional investment. The load varies periodically, but the peak current of power cable is controlled by its continuous ampacity in China, resulting in the highest conductor temperature is much lower than90℃, the permitted long-term working temperature of XLPE. If the cable load is controlled by its cyclic ampacity, the cable transmission capacity could be used sufficiently. To study the 10 kV XLPE cable cyclic ampacity and its factor, a three-core cable cyclic ampacity calculation software is developed and the cyclic ampacity experiments of direct buried cable are undertaken in this paper. Experiments and research shows that the software calculation is correct and the circuit numbers and daily load factor have an important impact on the cyclic ampacity factor. The cyclic ampacity factor of 0.7 daily load factor is 1.20, which means the peak current is the 1.2 times of continuous ampacity. If the continuous ampacity is instead by the cyclic ampacity to control the cable load, the transmission capacity of the cable can be improved greatly without additional investment.
出处 《Energy and Power Engineering》 2013年第4期1221-1225,共5页 能源与动力工程(英文)
关键词 XLPE CABLE EXPERIMENT CYCLIC AMPACITY Software XLPE Cable Experiment Cyclic Ampacity Software
  • 相关文献

参考文献2

二级参考文献16

  • 1刘毅刚,罗俊华.电缆导体温度实时计算的数学方法[J].高电压技术,2005,31(5):52-54. 被引量:88
  • 2楼开宏,秦一涛,施才华,张弘,魏德荣,蔡涵颖.基于光纤测温的电缆过热在线监测及预警系统[J].电力系统自动化,2005,29(19):97-99. 被引量:40
  • 3彭超,赵健康,苗付贵.分布式光纤测温技术在线监测电缆温度[J].高电压技术,2006,32(8):43-45. 被引量:125
  • 4罗俊华,周作春,李华春,罗旻.电力电缆线路运行温度在线检测技术应用研究[J].高电压技术,2007,33(1):169-172. 被引量:72
  • 5郑肇骥 王焜明.高压电缆线路[M].水利电力出版社,1983.350.
  • 6IEC 60287-1-1:1994 Calculation of the current rating of electric cables, part 1: current rating equations (100% load factor) and calculation of losses, sectionl: general[S], 1994.
  • 7IEC 60287-1 2:1993 Calculation of the current rating of elec- tric cables part 1: current rating equations (100% load factor) and calculation of losses, section 2 : sheath eddy current loss factor for two circuits in flat formation[S], 1993.
  • 8IEC 60287 2-1:1994 Calculation of the current rating of electric cables, part 2: thermal resistance, section 1: calculation of thermal resistance[S], 1994.
  • 9IEC 60287-3L1:1995 Calculation of the current rating of electric cables, part 3: sections on operating conditions, section 1: reference operating conditions and selection of cable type[S], 1995.
  • 10Anders G J. Rating of electric power cables: Ampaeity computations for transmission, distributions and industrial applications [M]. New York, USA: McGraw-Hill/IEEE Press, 1997.

共引文献73

同被引文献8

引证文献1

二级引证文献7

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部