Efficient Cooling System Using Electrocaloric Effect 被引量:2
1
作者 shigeki hirasawa Tsuyoshi Kawanami Katsuaki Shirai 《Journal of Electronics Cooling and Thermal Control》 2016年第2期78-87,共10页
The electrocaloric effect in thin films of an electrocaloric material has the potential to be used for efficient cooling systems for high power electronic devices. We numerically calculated the effect of parameters in... The electrocaloric effect in thin films of an electrocaloric material has the potential to be used for efficient cooling systems for high power electronic devices. We numerically calculated the effect of parameters in electrocaloric refrigeration with a thermal switch of fluid motion on the thermal performance. The system of changing air and water flow with the pulse generation of cold energy increased the heat transfer efficiency to 67% at a frequency of 5 Hz. The optimum time delay of water flow to increase the heat transfer efficiency was zero at low frequency and became half of the time period to change heat for a high frequency of 100 Hz. When the heat transfer efficiency was high, the final temperature change in water flow was not the maximum temperature change. 展开更多
关键词 Electrocaloric Refrigeration Thermal Switch OPTIMIZATION Pulse Heating FREQUENCY
下载PDF
Calculation Method for Forced-Air Convection Cooling Heat Transfer Coefficient of Multiple Rows of Memory Cards 被引量:2
2
作者 Takayuki Atarashi Tetsuya Tanaka +1 位作者 Shigeyasu Tsubaki shigeki hirasawa 《Journal of Electronics Cooling and Thermal Control》 2014年第3期70-77,共8页
Forced-air convection cooling of high-power electronic devices is widely used, but it has a problem that a rise in temperature of the air used to cool the upstream devices decreases the cooling capa-bility for the dow... Forced-air convection cooling of high-power electronic devices is widely used, but it has a problem that a rise in temperature of the air used to cool the upstream devices decreases the cooling capa-bility for the downstream devices. In this study we made an experimental apparatus including a memory card array and measured the effect of the rise in temperature of the air on the heat transfer coefficient of the memory cards that were downstream in the air flow. Using these mea-surements, we devised a simple calculation model, called the thermal diffusion layer model, to calculate the heat transfer coefficient of multiple rows of memory cards. The rise in temperature of downstream memory cards due to higher temperature air can be evaluated with a parameter representing the delay of thermal mixing for air. The heat transfer coefficient calculated with the thermal diffusion layer model agreed with our experimental results. 展开更多
关键词 FORCED CONVECTION Heat TRANSFER Performance LSI COOLING MEMORY Array
下载PDF
Temperature and Humidity Control in Greenhouses in Desert Areas
3
作者 shigeki hirasawa Mai Nakatsuka +2 位作者 Kunio Masui Tsuyoshi Kawanami Katsuaki Shirai 《Agricultural Sciences》 2014年第13期1261-1268,共8页
Water consumption can be reduced by using a greenhouse for agriculture in desert areas. We analyzed the effect of control of ventilation, sprinkler water, and solar radiation?shielding on changes of temperature and hu... Water consumption can be reduced by using a greenhouse for agriculture in desert areas. We analyzed the effect of control of ventilation, sprinkler water, and solar radiation?shielding on changes of temperature and humidity in a greenhouse under various desert area conditions. We calculated the changes in temperature and humidity in a greenhouse for a whole day in four seasons, and the calculation results of water consumption with and without a greenhouse were compared. When ventilation, shielding, and sprinkler water were controlled under suitable conditions to grow orchids in a desert area, water consumption in July was only 7% of that without a greenhouse. 展开更多
关键词 Temperature Control Humidity Ventilation SPRINKLER Water HEAT TRANSFER GREENHOUSE DESERT
下载PDF
Forced Convection Heat Transfer Coefficient and Pressure Drop of Diamond-Shaped Fin-Array
4
作者 shigeki hirasawa Atsushi Fujiwara +1 位作者 Tsuyoshi Kawanami Katsuaki Shirai 《Journal of Electronics Cooling and Thermal Control》 2014年第3期78-85,共8页
Forced convection cooling of fins on a high-temperature wall has been used to cool high-power electronic devices. We numerically calculated and experimentally measured the forced convection heat transfer coefficient a... Forced convection cooling of fins on a high-temperature wall has been used to cool high-power electronic devices. We numerically calculated and experimentally measured the forced convection heat transfer coefficient and pressure drop of a diamond-shaped fin-array with water flow in this study, which had been reported to have a self-induced flip-flop flow phenomenon. Although the flip-flop flow phenomenon occurred in calculations, it was not observed in experiments. The heat transfer and pressure drop of the diamond-shaped fin-array could be estimated with equations for turbulent flow in tubes. 展开更多
关键词 FORCED CONVECTION Heat Transfer Performance Diamond-Shaped FIN FLIP-FLOP Flow
下载PDF
Heat Transfer and Flow Analysis in Loop Heat Pipe with Multiple Evaporators Using Network Model
5
作者 shigeki hirasawa Tsuyoshi Kawanami Katsuaki Shirai 《Journal of Mechanics Engineering and Automation》 2016年第7期319-325,共7页
Thermal performance of a loop heat pipe with two evaporators and two condensers was examined using a lumped network model analysis. Thermosyphon-type vertical loop heat pipe and capillary-pump-type horizontal loop hea... Thermal performance of a loop heat pipe with two evaporators and two condensers was examined using a lumped network model analysis. Thermosyphon-type vertical loop heat pipe and capillary-pump-type horizontal loop heat pipe were calculated by examining the change of heating rate of two evaporators. Calculation results showed that the vapor and liquid flow rates in the loop heat pipe and the thermal conductance of the heat pipe changed significantly depending on the distribution ratio of the heating rate of the multiple evaporators. The thermal performance of the vertical loop heat pipe with two evaporators was also examined and experimental results of flow direction and thermal conductance of the heat pipe agreed with the analytical results. The lumped network model analysis is therefore considered accurate and preferable for the practical design of a loop heat pipe with multiple evaporators. 展开更多
关键词 Loop heat pipe multiple evaporators thermal conductance network model analysis two phase flow.