This paper deals with the experimental study on the correlation betweeninsulation resistance (R) and direct current (DC) component (i_(de)) and corresponding aging degreeof insulation in the course of the aging within...This paper deals with the experimental study on the correlation betweeninsulation resistance (R) and direct current (DC) component (i_(de)) and corresponding aging degreeof insulation in the course of the aging within cross linked polyethylene (XLPE) insulation. Theaging tests were performed on a section of 10 kV transmission XLPE cable by means of water needlemethod, and _R was measured by DC voltage superimposed method, R and i_(de) were found to besignificantly dependent on the correspondingaging degree of insulation in the course of aging ofXLPE, and different kind of aging stage has different characteristics. Beside, there are generallysimilar regularity but different amplitude in the course of aging of XLPE insulation in differentelectrolyte, and the various electrochemical tree were found on the surface of aging XLPE cableimmersed in CuSO_4, solution. Therefore, according to the changing regularity of the DCcharacteristic parameters i. e. R and i_(de) within XLPE insulation judging the aging degree of XLPEinsulation will be an effective method.展开更多
This paper deals with the experiemental study on the correlation between the geometrical parameters of electrical tree and corresponding partial discharge (PD) characteristic parameters in the course of eletrical tree...This paper deals with the experiemental study on the correlation between the geometrical parameters of electrical tree and corresponding partial discharge (PD) characteristic parameters in the course of eletrical tree aging within cross linked polyethylene (XLPE) insulation. The electrical tree aging tests were performed on specimens removed from a section of 220 kV transmission cable. The PD macroscopic characteristic parameters were found to be significantly dependent on the corresponding geometrical parameters of eletrical tree channels in the course of aging of XLPE, and different kind of electrical tree has different characteristics, and there is obvious correlation between the type of electrical tree and the pre-applied power-frequency stress. Beside, using regression analysis, the expression of the relation between them were obtained, and from which it can be seen that there is significant nonlinear correlation between geometrical parameters of electrical tree and corresponding PD characteristic parameters in the course of aging of XLPE. Therefore, the aging degree of XLPE can be effectively evaluated by recognizing the changing regularity of the PD macroscopic characteristic parameters. Key words XLPE - electrical tree aging - partial discharge - mathematical model CLC number TM 121 Foundation item: Supported by the National Natural Science Foundation of China (59677018)Biography: Wang Hong-xin (1963-), male, Associate professor, Postdoctoral fellows, research direction: electrical insulation condition monitoring, EMC展开更多
基金Supported by the National Natural Science Foundation of China (59677018)
文摘This paper deals with the experimental study on the correlation betweeninsulation resistance (R) and direct current (DC) component (i_(de)) and corresponding aging degreeof insulation in the course of the aging within cross linked polyethylene (XLPE) insulation. Theaging tests were performed on a section of 10 kV transmission XLPE cable by means of water needlemethod, and _R was measured by DC voltage superimposed method, R and i_(de) were found to besignificantly dependent on the correspondingaging degree of insulation in the course of aging ofXLPE, and different kind of aging stage has different characteristics. Beside, there are generallysimilar regularity but different amplitude in the course of aging of XLPE insulation in differentelectrolyte, and the various electrochemical tree were found on the surface of aging XLPE cableimmersed in CuSO_4, solution. Therefore, according to the changing regularity of the DCcharacteristic parameters i. e. R and i_(de) within XLPE insulation judging the aging degree of XLPEinsulation will be an effective method.
文摘This paper deals with the experiemental study on the correlation between the geometrical parameters of electrical tree and corresponding partial discharge (PD) characteristic parameters in the course of eletrical tree aging within cross linked polyethylene (XLPE) insulation. The electrical tree aging tests were performed on specimens removed from a section of 220 kV transmission cable. The PD macroscopic characteristic parameters were found to be significantly dependent on the corresponding geometrical parameters of eletrical tree channels in the course of aging of XLPE, and different kind of electrical tree has different characteristics, and there is obvious correlation between the type of electrical tree and the pre-applied power-frequency stress. Beside, using regression analysis, the expression of the relation between them were obtained, and from which it can be seen that there is significant nonlinear correlation between geometrical parameters of electrical tree and corresponding PD characteristic parameters in the course of aging of XLPE. Therefore, the aging degree of XLPE can be effectively evaluated by recognizing the changing regularity of the PD macroscopic characteristic parameters. Key words XLPE - electrical tree aging - partial discharge - mathematical model CLC number TM 121 Foundation item: Supported by the National Natural Science Foundation of China (59677018)Biography: Wang Hong-xin (1963-), male, Associate professor, Postdoctoral fellows, research direction: electrical insulation condition monitoring, EMC