Transient Ablation Regime in Circuit Breakers 被引量:1
1
作者 alexandre martin Jean-Yves TREPANIER Marcelo REGGIO 《Plasma Science and Technology》 SCIE EI CAS CSCD 2007年第6期653-656,共4页
Nozzle wall ablation caused by high temperature electric arcs is studied in the context of high voltage SF6 circuit breakers. The simplified ablation model used in litterature has been updated to take into account the... Nozzle wall ablation caused by high temperature electric arcs is studied in the context of high voltage SF6 circuit breakers. The simplified ablation model used in litterature has been updated to take into account the unsteady state of ablation. Ablation rate and velocity are now calculated by a kinetic model using two layers of transition, between the bulk plasma and the ablating wall. The first layer (Knudsen layer), right by the wall, is a kinetic layer of a few mean-free path of thickness. The second layer is collision dominated and makes the transition between the kinetic layer and the plasma bulk. With this new coupled algorithm, it is now possible to calculate the temperature distribution inside the wall, as well as more accurate ablation rates. 展开更多
关键词 circuit breakers electric arc ablation TEFLON RADIATION