This paper aims to find a more general analysis method for the refrigeration performance,and to design a high efficiency modular cooling structure of water-cooled plate.A new analysis method,namely current and refrige...This paper aims to find a more general analysis method for the refrigeration performance,and to design a high efficiency modular cooling structure of water-cooled plate.A new analysis method,namely current and refrigeration rate density analysis,is proposed.The general refrigeration performance calculation equations are obtained.A finite-time thermodynamic model of the thermoelectric device is established considering Thomson effect.The basic structure of water-cooled thermoelectric air-conditioner is designed and the specific calculation method is given.The influences of input current density,filling factor and heat transfer conditions on refrigeration performance of the thermoelectric air-conditioner are analyzed,which is compared with refrigeration performance of air-cooled thermoelectric air-conditioner.The results show that the maximum refrigeration rate density of the water-cooled thermoelectric air-conditioner is 8.65 k W/m^(2),and the maximum coefficient of performance(COP)is 2.27 in the case of the cooling temperature differenceΔT=5 K.Compared withΔT=5 K,the maximum refrigeration rate density and the maximum COP ofΔT=15 K decreases by 27.98%and 76.65%,respectively.At the filling factorθ=0.43,the refrigeration rate density and COP are 2.57 k W/m~2 and 1.24,respectively.The experimental device of thermoelectric air-conditioner is established to verify the model.The experimental results show that the maximum value of input current and COP is 4 A and 0.95 with the efficient water-cooling method,respectively.The experimental data coincides with the theoretical calculation,which shows the validity of the analysis method and cooling method.展开更多
基金supported by The National Natural Science Foundation of P.R.China(Project No.11974429 and Project No.51576207)the Natural Science Foundation of Naval University of Engineering(20161505)。
文摘This paper aims to find a more general analysis method for the refrigeration performance,and to design a high efficiency modular cooling structure of water-cooled plate.A new analysis method,namely current and refrigeration rate density analysis,is proposed.The general refrigeration performance calculation equations are obtained.A finite-time thermodynamic model of the thermoelectric device is established considering Thomson effect.The basic structure of water-cooled thermoelectric air-conditioner is designed and the specific calculation method is given.The influences of input current density,filling factor and heat transfer conditions on refrigeration performance of the thermoelectric air-conditioner are analyzed,which is compared with refrigeration performance of air-cooled thermoelectric air-conditioner.The results show that the maximum refrigeration rate density of the water-cooled thermoelectric air-conditioner is 8.65 k W/m^(2),and the maximum coefficient of performance(COP)is 2.27 in the case of the cooling temperature differenceΔT=5 K.Compared withΔT=5 K,the maximum refrigeration rate density and the maximum COP ofΔT=15 K decreases by 27.98%and 76.65%,respectively.At the filling factorθ=0.43,the refrigeration rate density and COP are 2.57 k W/m~2 and 1.24,respectively.The experimental device of thermoelectric air-conditioner is established to verify the model.The experimental results show that the maximum value of input current and COP is 4 A and 0.95 with the efficient water-cooling method,respectively.The experimental data coincides with the theoretical calculation,which shows the validity of the analysis method and cooling method.