Live-Grid Operation and Maintenance of the 35 kV/121 MVA Superconducting Cable System
1
作者 huan-huan li an-lin ren ying xin hui hong zhi-li chen lin-na shi 《Journal of Electronic Science and Technology of China》 2008年第2期108-111,共4页
A 33.5 m, 35 kV/121 MVA, three-phase, warm dielectric HTS power cable system was successfully installed and activated in China Southern Power Grid at the Puji substation in Kunming on April 19th of 2004, supplying ele... A 33.5 m, 35 kV/121 MVA, three-phase, warm dielectric HTS power cable system was successfully installed and activated in China Southern Power Grid at the Puji substation in Kunming on April 19th of 2004, supplying electricity to four industrial customers (including two metallurgical refineries) and a residential population of about 100000. In this paper, we give an update on the operation and maintenance status of the system and comments on reliability issues. We conclude that the superconducting cable system is currently quite robust and feasible for particular utility applications, and it will be improved by advancement in cryogenic equipment and system technology. 展开更多
关键词 Power grid power transmission superconductivity superconducting cable.