期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
Analysis of condenser venting rates based on the air mass entransy increases 被引量:5
1
作者 ji’an meng Hui Zeng Zhixin Li 《Chinese Science Bulletin》 SCIE EI CAS 2014年第26期3283-3291,共9页
Condenser thermal performances, such as the back pressure and venting rate, are strongly affected by the tube arrangement. Condensers have three irreversible processes for the fluid flow, heat transfer and mass diffus... Condenser thermal performances, such as the back pressure and venting rate, are strongly affected by the tube arrangement. Condensers have three irreversible processes for the fluid flow, heat transfer and mass diffusion.The condenser venting rate is studied here based on an air mass entransy analysis. The air mass entransy increment rate for the steam and air mixture on the condenser shell side is expressed as a function of the distributed air mass fraction and the steam condensation rate to define the relationship between the condenser venting rate and the flow parameters. Condensers with three typical tube arrangements were analyzed numerically using the porous medium model. The results show that a bigger venting rate always corresponds to a smaller air mass entransy increment rate. The air mass entransy generally decreases in the air concentration region and increases in the air cooling region under the combined action of the air diffusion and steam condensation. The numerical results indicate that the air cooling region of a condenser should be carefully designed and the cooling tubes should be properly arranged to guide the steam flow so as to weaken air concentration,and consequently to decrease the venting rate. 展开更多
关键词 冷凝器 通风率 气团 基础 空气混合物 空气冷却区 排气速度 多孔介质模型