Design of Mechanical Smoke Exhaust System in Large Space of Convention Center 被引量:1
1
作者 jung-yup kim Chan-Sol Ahn 《Open Journal of Fluid Dynamics》 2017年第3期386-396,共11页
The volumetric flow rate of smoke generated from the fire in large space often reaches to hundreds of thousands CMH because of extended floor height and as it’s more difficult to isolate the smoke to the limited area... The volumetric flow rate of smoke generated from the fire in large space often reaches to hundreds of thousands CMH because of extended floor height and as it’s more difficult to isolate the smoke to the limited area, comparing to normal-scale building, design and operation of effective smoke control system for large space is more than important. In this study, with the analysis model for such a large space as exhibition hall or conference room in conventional center, design of mechanical smoke exhaust system was conducted based on currently-available design standard which was then followed by numerical analysis of the design using 3D numerical analysis method. For conference room at 2.0 MW heat release rate, 99,173 CMH flow rate is required, if smoke layer is maintained at 60% of the floor height and for exhibition hall at 8.8 MW with 80% of floor height, flow rate required is 219,802 CMH, which are incorporated into the design. In view of 3D numerical analysis, accuracy of the design according to algebraic expression is sufficient. 展开更多
关键词 SMOKE Control Mechanical EXHAUST SYSTEM Large Space CONVENTION CENTER NUMERICAL Analysis
下载PDF
Study on Stack Effect of Stairwell by Numerical Model of Leakage Flow through Gap of Door
2
作者 jung-yup kim Ji-Seok kim 《Open Journal of Fluid Dynamics》 2013年第4期241-247,共7页
Since stack effect that occurs in high-rise buildings has an effect on the indoor environment of the buildings, energy loss and smoke control in case of a fire, there is a need to conduct research on this. For an anal... Since stack effect that occurs in high-rise buildings has an effect on the indoor environment of the buildings, energy loss and smoke control in case of a fire, there is a need to conduct research on this. For an analysis of the stack effect, analysis methods on the leakage flow through gap of interior door shall be formulated. Until now, studies related to the gap leakage flow in buildings have mainly analyzed flow field and pressure in the buildings one-dimensionally using pressure difference-leakage flowrate relations of Orifice Equation and a network numerical analysis algorithm that as- sumes each compartment in the buildings as a single point. In this study, the Momentum Loss Model which enables pressure drop to be proportional to the flow velocity through the gap of door in computational domain of 3-dimensional numerical analysis was proposed to reflect the gap flow phenomenon effectively in 3-dimensional numerical analysis. Using the proposed model, 3-dimensional numerical analysis of the stack effect on the stairs in buildings was performed, and the effects of separation door and lobby between stair and accommodation on the stack effect were investigated. 展开更多
关键词 STACK Effect LEAKAGE Flow GAP of DOOR MOMENTUM Loss Model Separation DOOR NUMERICAL Analysis
下载PDF
Study on Design of Pressure Chamber in a Linear-Jet Type Air Curtain System for Prevention of Smoke Spread
3
作者 jung-yup kim Su-Gak Lee 《Open Journal of Fluid Dynamics》 2017年第4期501-510,共10页
Death toll by smoke in fire is estimated at 70% which emphasizes the importance of smoke control system to deal with the fire smoke. In advanced countries, the studies on method to prevent smoke spread by forming the ... Death toll by smoke in fire is estimated at 70% which emphasizes the importance of smoke control system to deal with the fire smoke. In advanced countries, the studies on method to prevent smoke spread by forming the air curtain using high velocity jet flow are underway now. In this study, a linear-jet type air curtain system is proposed to prevent the smoke spread and analysis of flow characteristics of pressure chamber, which is the core component, is conducted through numerical analysis and experimental approach. Consequently, the pressure was increased in 2D functional way to input air flowrate and about 595 Pa pressure was formed at pressure chamber inlet in response to 30 m/s nozzle jet velocity. 展开更多
关键词 SMOKE Spread PREVENTION LINEAR JET Air CURTAIN SYSTEM Fire Numerical Analysis Experiment
下载PDF
Development of the Separate Air-Supply Type of Pressurization Smoke Control System for the Stairwells of High-Rise Buildings in Korea
4
作者 jung-yup kim Hyun-Joon Shin +2 位作者 Chan-Sol Ahn Ji-Seok kim Sang-Hyun Joo 《Open Journal of Fluid Dynamics》 2014年第3期251-262,共12页
The pressurization smoke control system has been commonly used as a smoke control system at the emergency stairs of high-rise buildings. However, a higher possibility of overpressure between the lobby and the accommod... The pressurization smoke control system has been commonly used as a smoke control system at the emergency stairs of high-rise buildings. However, a higher possibility of overpressure between the lobby and the accommodation or pressure drop in the lobby could lead to failure in achievement of the purpose of pressurization system, particularly when supplying the leakage and supplementary air flow through one air-supply path at a time. To improve this particular issue, the devise configurations, as well as the different ways to supply the leakage and supplementary air flow through the different flow passages have been proposed. The performance of the trial product was evaluated on the test bed, ultimately providing a safe evacuation environment if high-rise buildings fired. 展开更多
关键词 PRESSURIZATION System SMOKE Control HIGH-RISE Building EVACUATION STAIRWELL Field EXPERIMENT
下载PDF
Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan
5
作者 jung-yup kim 《Open Journal of Fluid Dynamics》 2017年第2期205-218,共14页
In houses and general buildings of environment where smoke control equipment is not installed, or its operation is difficult, there is a need to develop and utilize a portable smoke exhaust fan that can perform emerge... In houses and general buildings of environment where smoke control equipment is not installed, or its operation is difficult, there is a need to develop and utilize a portable smoke exhaust fan that can perform emergency ventilation in case of fire suppression and rescue operations. As a part of the development process for portable smoke exhaust fans, a numerical analysis model of the portable smoke exhaust fan was derived from the building in which a fire occurred, and an analysis on the smoke and toxic gas exhaust effects was performed in this study. The numerical analysis results showed that under a condition where the height of an opening is less than 1.0 m after fire source disappears in a situation where the smoke exhaust fan does not operate, smoke does not come out well, and thus the density of smoke within the target area does not drop significantly. On the other hand, if the smoke exhaust fan operates after the fire source disappears, smoke is directly exhausted to the outside due to the operation of the smoke exhaust fan, and the smoke density within the space drops sharply in all opening height conditions, thereby getting close to zero. 展开更多
关键词 SMOKE EXHAUST PORTABLE FAN SMOKE DENSITY CO DENSITY Numerical Analysis