Accurate simulation of lightning-induced overvoltage for overhead distribution lines is helpful to prevent lightning trip accidents.An electromagnetic return-stroke model was used to represent lightning and then a 3D ...Accurate simulation of lightning-induced overvoltage for overhead distribution lines is helpful to prevent lightning trip accidents.An electromagnetic return-stroke model was used to represent lightning and then a 3D finite-difference time-domain(FDTD)method was adopted to simulate the lightning-induced overvoltage on a distribution line without a field-line coupling model.How lightning-induced overvoltage behave for different ground conductivity and varying distance between the distribution line and the lightning channel was analysed.The results showed that the overvoltage waveforms at the centre point of the line corresponding to lightning strikes on the lossy ground and an ideal ground(σ=∞)were similar;however,the peak amplitudes of the waveform were affected by soil conductivity at a close distance.The relationship between magnitude of the overvoltage and distance can be described by a second-order exponential decay equation.Finally,the overvoltage calculated using the proposed model was compared with those obtained based on Agrawal's model and measurements made using the newly developed intelligent insulator on site.From these comparisons,it could be concluded that the FDTD method with the electromagnetic return-stroke model produces reasonably accurate results of the attenuated oscillation waveform,which can better reproduce the overvoltage on operational distribution lines.展开更多
基金National Natural Science Foundation of China,Grant/Award Number:51807018Natural Science Foundation of Chongqing,Grant/Award Number:cstc2020jcyj-msxmX0054。
文摘Accurate simulation of lightning-induced overvoltage for overhead distribution lines is helpful to prevent lightning trip accidents.An electromagnetic return-stroke model was used to represent lightning and then a 3D finite-difference time-domain(FDTD)method was adopted to simulate the lightning-induced overvoltage on a distribution line without a field-line coupling model.How lightning-induced overvoltage behave for different ground conductivity and varying distance between the distribution line and the lightning channel was analysed.The results showed that the overvoltage waveforms at the centre point of the line corresponding to lightning strikes on the lossy ground and an ideal ground(σ=∞)were similar;however,the peak amplitudes of the waveform were affected by soil conductivity at a close distance.The relationship between magnitude of the overvoltage and distance can be described by a second-order exponential decay equation.Finally,the overvoltage calculated using the proposed model was compared with those obtained based on Agrawal's model and measurements made using the newly developed intelligent insulator on site.From these comparisons,it could be concluded that the FDTD method with the electromagnetic return-stroke model produces reasonably accurate results of the attenuated oscillation waveform,which can better reproduce the overvoltage on operational distribution lines.