期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
Investigation on insulation properties of HFO-1336mzz(E)and N_(2)/CO_(2)mixtures as SF_(6) substitutes in gas-insulated electrical applications 被引量:3
1
作者 Zhanyang Gao Yunbai Luo +3 位作者 ruichao peng Xiaoxiao Wang Ping Yu Wenjun Zhou 《High Voltage》 SCIE EI CSCD 2023年第1期48-58,共11页
The emissions of SF6 have been restricted owing to 3400 years of atmospheric lifetime and high global warming potential(GWP)as an insulating gas in gas-insulated electrical equipment.In this study,HFO-1336mzz(E)and N_... The emissions of SF6 have been restricted owing to 3400 years of atmospheric lifetime and high global warming potential(GWP)as an insulating gas in gas-insulated electrical equipment.In this study,HFO-1336mzz(E)and N_(2)/CO_(2)mixtures are proposed as SF6 substitutes for their short atmospheric lifetime,low GWP and superior insulation performance.The GWP of HFO-1336mzz(E)is only 18 and its atmospheric lifetime is days to weeks.The breakdown voltage of 25%HFO-1336mzz(E)and N_(2)/CO_(2)mixtures is about 85%that of pure SF6 under alternating current.The self-recovery ability of HFO-1336mzz(E)and CO_(2)mixtures is superior to that of HFO-1336mzz(E)and N_(2)mixtures.The decomposition characteristic of HFO-1336mzz(E)shows that a tiny amount of its gas might initiate a carbonisation reaction to form carbon after multiple breakdown tests,which is verified by observations using energy dispersive X-rays spectroscopy and scanning electron microscope.The acute toxicity test of HFO-1336mzz(E)indicates that the gas is non-toxic.The results show that HFO-1336mzz(E)and N_(2)/CO_(2)mixtures are potential substitutes for SF6 in electrical applications. 展开更多
关键词 SF6 ELECTRICAL INSULATION
原文传递