Experimental studies on impedance based fault location for long transmission lines
1
作者 saeed roostaee Mini S.Thomas Shabana Mehfuz 《Protection and Control of Modern Power Systems》 2017年第1期169-177,共9页
In long transmission lines,the charging current caused by the shunt capacitance decreases the accuracy in impedance based fault location.To improve the accuracy of fault location,this paper presents a novel scheme,whe... In long transmission lines,the charging current caused by the shunt capacitance decreases the accuracy in impedance based fault location.To improve the accuracy of fault location,this paper presents a novel scheme,where two Digital Fault Recorders(DFRs)are installed in a line.They can send the transient data of the faults to the both ends of a line.To estimate the distance of a fault,impedance based fault location methods are applied with transient fault data of both ends protection relays and both DFRs installed in a line.To evaluate the proposed scheme,a laboratory setup has been developed.In the lab,several faults have been simulated and associated voltages and currents are injected to a relay IED to compare experimental results. 展开更多
关键词 Transmission line fault location Impedance based fault location