The breakdown voltage of long air-gaps in high-voltage transmission systems depends on not only the waveform of the applied voltage, but also the atmospheric conditions. Based on the results of the research project on...The breakdown voltage of long air-gaps in high-voltage transmission systems depends on not only the waveform of the applied voltage, but also the atmospheric conditions. Based on the results of the research project on the minimum air clearance for 800-kV HVDC substations at high altitudes, and also on the monthly and yearly statistics of the atmospheric data of last ten years and the altitude correction of the atmospheric data of last ten years, the altitude correction of the air-gaps for the 800-kV DC system under plan, 500-kV AC system to be built, and 1000-kV AC system under plan in the Inner Mongolia Plateau and the Yungui Plateau in China were studied with parameter G method. Correction factors for switching and lightning impulses were calculatod and then compared with those achieved according to IEC 71. It is shown that IEC 71 is appropriate for damp regions, and correction factors differ between plateau regions in China because of different atmospheric conditions.展开更多
文摘The breakdown voltage of long air-gaps in high-voltage transmission systems depends on not only the waveform of the applied voltage, but also the atmospheric conditions. Based on the results of the research project on the minimum air clearance for 800-kV HVDC substations at high altitudes, and also on the monthly and yearly statistics of the atmospheric data of last ten years and the altitude correction of the atmospheric data of last ten years, the altitude correction of the air-gaps for the 800-kV DC system under plan, 500-kV AC system to be built, and 1000-kV AC system under plan in the Inner Mongolia Plateau and the Yungui Plateau in China were studied with parameter G method. Correction factors for switching and lightning impulses were calculatod and then compared with those achieved according to IEC 71. It is shown that IEC 71 is appropriate for damp regions, and correction factors differ between plateau regions in China because of different atmospheric conditions.