期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
放电对变压器油特性的影响(英文)
1
作者 J.S.N'Cho I.Fofana +1 位作者 t.aka-ngnui A.Beroual 《高电压技术》 EI CAS CSCD 北大核心 2011年第11期2793-2799,共7页
Petroleum based oils,the so-called mineral oils,are used for impregnating solid insulations or filling products of very large number of electric materials:transformers,reactors,cables,bushings,circuit breakers,tap cha... Petroleum based oils,the so-called mineral oils,are used for impregnating solid insulations or filling products of very large number of electric materials:transformers,reactors,cables,bushings,circuit breakers,tap changers, etc.In these equipments,oil is exposed to electrical stress and may experience electrical discharges under certain circumstances.Since the electrical stress is unavoidable in power equipments,the ability of oil to resist decomposition under electrical stress is of great importance for the safety of these devices.Electrical stress together with heat and moisture,in the presence of oxygen,oxidises the oil producing free radicals,acids and sludge that are deleterious to the transformer.In this paper,the effect of electrical discharges on oil properties is reported.The results indicate that quality of oil is considerably affected with increasing voltage stress.Comparing oil properties before and after voltage application allows assessing the outcome of random secondary chemical reactions between large oil born free radicals. 展开更多
关键词 electrical discharge oil transformer dielectric dissipation factor(DDF) CONDUCTIVITY dissolved decay products TURBIDITY interfacial tension total acid number water content
下载PDF
上一页 1 下一页 到第
使用帮助 返回顶部