The thermodynamic cycle for an adsorption system is presented inp-T diagram. In order to investigate the performance of the adsorption system, a lumped parameter transient model of the chiller is developed, in order t...The thermodynamic cycle for an adsorption system is presented inp-T diagram. In order to investigate the performance of the adsorption system, a lumped parameter transient model of the chiller is developed, in order to predict the behaviors of the adsorption chiller system and find the influence of working conditions on its operation. For the working process of the main components of the system, including adsorber, condenser and evaporator, the coupled unsteady equations were set up for each stage. The model was then solved using stable numerical methods from EES (equation engineering solver), and the performance of the adsorber and condenser/evaporator of the system was analyzed. The condensation, evaporation and adsorber temperature values as well as the adsorption ratio and desorption ratio were obtained as function of operating time. Also, the coefficient of performance was analyzed in function of the heat source temperature and the cooling source temperature.展开更多
文摘The thermodynamic cycle for an adsorption system is presented inp-T diagram. In order to investigate the performance of the adsorption system, a lumped parameter transient model of the chiller is developed, in order to predict the behaviors of the adsorption chiller system and find the influence of working conditions on its operation. For the working process of the main components of the system, including adsorber, condenser and evaporator, the coupled unsteady equations were set up for each stage. The model was then solved using stable numerical methods from EES (equation engineering solver), and the performance of the adsorber and condenser/evaporator of the system was analyzed. The condensation, evaporation and adsorber temperature values as well as the adsorption ratio and desorption ratio were obtained as function of operating time. Also, the coefficient of performance was analyzed in function of the heat source temperature and the cooling source temperature.