Different aerodynamics calculation methods for three designed cooling towers are compared. Verifications are made by using the field test data of the three operating cooling towers. It is proposed that the wind effect...Different aerodynamics calculation methods for three designed cooling towers are compared. Verifications are made by using the field test data of the three operating cooling towers. It is proposed that the wind effects on water temperature after cooled by tower shall be considered in the cooling tower design; the Hamon calculation method is one of the feasible method; the method of adding the resistance coefficients of various parts of cooling tower should not be used.展开更多
文摘Different aerodynamics calculation methods for three designed cooling towers are compared. Verifications are made by using the field test data of the three operating cooling towers. It is proposed that the wind effects on water temperature after cooled by tower shall be considered in the cooling tower design; the Hamon calculation method is one of the feasible method; the method of adding the resistance coefficients of various parts of cooling tower should not be used.