The Research on Grounding Protection for 110kV Resistance Grounding Distribution System 被引量:1
1
作者 Shan Sun Guo Zeng +2 位作者 xiaozang he Yanping Lv Xinyi Li 《Energy and Power Engineering》 2013年第4期877-880,共4页
Using the neutral grounding method by the resistance in 110?kV system, it can limit the voltage sag and short circuit current when one-phase grounding fault occurred, but it will change the sequence of the network str... Using the neutral grounding method by the resistance in 110?kV system, it can limit the voltage sag and short circuit current when one-phase grounding fault occurred, but it will change the sequence of the network structure and parameters. This paper analyzes the size and distribution of zero sequence voltage and current when one-phase grounding fault occurred in the 110 kV resistance grounding system, and puts forward the grounding protection configuration setting principle of this system combining the power supplying characteristics of 110?kV distribution network. In a reforming substation as an example, the grounding protection of 110 kV lines and transformer have been set and calculated. 展开更多
关键词 Neutral GROUNDING System by Resistance One-phase GROUNDING Fault ZERO SEQUENCE Voltage ZERO SEQUENCE Current PROTECTION Setting