A SFC-ES (Electrostatic Deflection) position monitoring and limit alarm system was built in 2014. As planned, the motion control part of SFC-ES is going to be upgraded and joined into this system in 2015 to complete a...A SFC-ES (Electrostatic Deflection) position monitoring and limit alarm system was built in 2014. As planned, the motion control part of SFC-ES is going to be upgraded and joined into this system in 2015 to complete a closed loop motion control system[1]. During the HIRFL 2015 summer maintains, this motion control function was realized and tested several times before used to verify the control and detection precision. At present, the overall control accuracy is about 0.2 mm.展开更多
Heavy ion therapy for cancer treatment is known as the world’s most advanced and most effective radiotherapy method. Institute of Modern Physics, Chinese Academy of Sciences spent a long time to research in this fiel...Heavy ion therapy for cancer treatment is known as the world’s most advanced and most effective radiotherapy method. Institute of Modern Physics, Chinese Academy of Sciences spent a long time to research in this field. The beam of Chinese first medical heavy ion accelerator with independent intellectual property rights was successfully extracted on December 23rd, 2015 in Wuwei. Medical heavy ion accelerator is a huge system; this paper only describes the ion-source and cyclotron control software design.展开更多
The kicker system in the Heavy Ion Research Facility in Lanzhou (HIRFL) plays an important role in beam extraction and injection between two cooling storage rings (CSRs). The old kicker control system which has been o...The kicker system in the Heavy Ion Research Facility in Lanzhou (HIRFL) plays an important role in beam extraction and injection between two cooling storage rings (CSRs). The old kicker control system which has been operated over 5 years cannot satisfy the requirements of current special physics experiments. The main reason is the 5 ns time precision restricts the improvement of the precision for the phase detection of the beam bunches.展开更多
To improve the control efficiency of Superconducting Electron Cyclotron Resonance Ion source (SECRAL) forHeavy Ion Research Facility in Lanzhou (HIRFL), a upgrade version of control system for SECRAL system wasdesigne...To improve the control efficiency of Superconducting Electron Cyclotron Resonance Ion source (SECRAL) forHeavy Ion Research Facility in Lanzhou (HIRFL), a upgrade version of control system for SECRAL system wasdesigned and set up in September 2014. The control software package is developed by Visual C++, which is ableto control and monitor all of the equipment for the SECRAL system with about 130 parameters. The previousanalog powers are discarded and four digital high powers are used newly at high voltage platform, which containtwo stove powers, a bias voltage power, and a sputter power. Moreover, four servo motors are added newly, whichcontain work gas, support gas, bias voltage, and sputter voltage. Reflecting vacuum value picturesquely, we plot agraph of inject vacuum, elicit vacuum, and beam vacuum against time. In order to prevent the misoperation whichmay cause the quench of the superconducting magnet, alarm and interlock-protection functions are added to thesoftware and hardware. Simultaneously, added stretch buttons are able to void accidental on-click that might bringabout serious outcome.展开更多
The SFC extraction electrostatic deflection plate is located inside the SFC chamber and it is responsible for theSFC beam extraction. Before the SFC-ES position monitoring system was build, the actual position of the ...The SFC extraction electrostatic deflection plate is located inside the SFC chamber and it is responsible for theSFC beam extraction. Before the SFC-ES position monitoring system was build, the actual position of the cuttingpole and the high voltage cathode pole cannot be "seen" for beam tuning stuff. So they can only tuning the beam"blindly". This is very dangerous, in case of over adjusting the pole, serious damage may be caused. To avoid thiskind of damage, a route limit monitoring system was built in 2012. Using this system, the beam tuning stuff canget the information whether the cutting pole/the high voltage cathode pole is reaching the route limit. If the polehas reached the limit, there will be alarm information in the GUI interface to inform the beam tuning stuff to stopthe motor and change the moving direction. Although this can prevent big damage, precision position detectionfunction cannot be reached, and the SFC extraction electrostatic deflection plate still should be pulled out to checkthe position manually.展开更多
High Intensity Heavy-ion Accelerator Facility(HIAF)is a very complex and huge system which is under construction by the Institute of Modern Physics in Huizhou.In order to realize the safe and reliable operation of thi...High Intensity Heavy-ion Accelerator Facility(HIAF)is a very complex and huge system which is under construction by the Institute of Modern Physics in Huizhou.In order to realize the safe and reliable operation of this facility.展开更多
DR(Dielectronic Recombination)and CSRe cluster internal target are two of the important experiment terminals in HIRFL(Heavy Ion Research Facility in Lanzhou).Both terminals have moving detectors,which need to be pushe...DR(Dielectronic Recombination)and CSRe cluster internal target are two of the important experiment terminals in HIRFL(Heavy Ion Research Facility in Lanzhou).Both terminals have moving detectors,which need to be pushed in or pulled out remotely.Since the old control system has lot of inconvenience such as the decline of control accuracy and running instability,a set of new motion control system is design and realized in 2018.展开更多
To establish the sputter ion pump remote control system for TR5 and TR6 of HIRFL(Heavy Ion Research Facility in Lanzhou),EPICS(Experimental Physics And Industrial Control System)is adopted to development new control s...To establish the sputter ion pump remote control system for TR5 and TR6 of HIRFL(Heavy Ion Research Facility in Lanzhou),EPICS(Experimental Physics And Industrial Control System)is adopted to development new control system.Beckhoff PLC and self-designed hardware module have been used to build the hardware platform and the whole system structure is established based on field bus and EtherCAT(Ethernet for Control Automation Technology)technology.EtherCAT is an ideal Ethernet solution for industrial automation,characterized by outstanding performance and particularly simple handling.In the realization process of the system,IOC record device support and PV definition are achieved.At the same time,we have developed a client application in the CSS environment.In this sputter ion pump control system,we realized the basic interlocking protection function in both of hardware and software.The photo of hardware module is shown in Fig.1.The GUI interface is shown in Fig.2.The control system has being stably run since installed in Aug.2017.展开更多
To improve the control efficiency of Ion source for HIRFL,upgrade versions of control systems for ECR and SECRAL were designed and set up in August 2017.The control software packages were developed by Visual C++platfo...To improve the control efficiency of Ion source for HIRFL,upgrade versions of control systems for ECR and SECRAL were designed and set up in August 2017.The control software packages were developed by Visual C++platform.The control softwares were designed as independent classes.Thus,new devices can be easily added.The control systems were completed and became operational in September 2017.The developed systems have been used successfully for providing various types of beams for physical experiments.展开更多
For personal protection purposes,the slow control group designed a radiation dose monitor system and a gate controller with the radiation protection group in HIRFL-CSR.These two works are listed one by one in this art...For personal protection purposes,the slow control group designed a radiation dose monitor system and a gate controller with the radiation protection group in HIRFL-CSR.These two works are listed one by one in this article.1.The radiation dose monitor system For radiation protection purposes,the environment radiation dose monitoring is important.According to the characteristics of the detector,self-designed hardware module and switch have been used to build the hardware platform and the whole monitoring system structure is established base on field bus and Ethernet technology.展开更多
In motion control area,safety consideration while the moving part touches the limit switch is very important.Otherwise there might be device damage if the moving parts still move toward the limit switch after it touch...In motion control area,safety consideration while the moving part touches the limit switch is very important.Otherwise there might be device damage if the moving parts still move toward the limit switch after it touches the switch.In the SFC extraction electrostatic spectrum motion control project[1]and the Xi’an 200 MeV proton device electrostatic spectrum motion control work,we realized the limit position protection function using Phoenix PLC and Rockwell Allen Bradley(AB)PLC.In the Phoenix PLC,a function block is designed using ST language.In the AB PLC,ladder logic programming language is used to realize the function.展开更多
Background Ion pump control system of HIRFL is designed based on the real-time distributed control software,EPICS.The hardware architecture,communication principle,database design and interlock design are introduced a...Background Ion pump control system of HIRFL is designed based on the real-time distributed control software,EPICS.The hardware architecture,communication principle,database design and interlock design are introduced and elaborated in the paper.Methods PLC has been adopted to realize functions such as control monitoring and data communication.Interlock protect ion has been designed for ion pump control system to prevent damaging from high voltage.Results The test results show that the system has fast response function and high-speed data processing during the beam running and tuning.The response time of the system could reach 100 ms,the rate of data acquisition reaches to 10 time/s and the interlock protection time less than 40 ms.Conclusion The reliable and stable long-term operation of the vacuum system indicates that the performance has been constantly improved with the continuous optimization of the ion pump control system.展开更多
文摘A SFC-ES (Electrostatic Deflection) position monitoring and limit alarm system was built in 2014. As planned, the motion control part of SFC-ES is going to be upgraded and joined into this system in 2015 to complete a closed loop motion control system[1]. During the HIRFL 2015 summer maintains, this motion control function was realized and tested several times before used to verify the control and detection precision. At present, the overall control accuracy is about 0.2 mm.
文摘Heavy ion therapy for cancer treatment is known as the world’s most advanced and most effective radiotherapy method. Institute of Modern Physics, Chinese Academy of Sciences spent a long time to research in this field. The beam of Chinese first medical heavy ion accelerator with independent intellectual property rights was successfully extracted on December 23rd, 2015 in Wuwei. Medical heavy ion accelerator is a huge system; this paper only describes the ion-source and cyclotron control software design.
文摘The kicker system in the Heavy Ion Research Facility in Lanzhou (HIRFL) plays an important role in beam extraction and injection between two cooling storage rings (CSRs). The old kicker control system which has been operated over 5 years cannot satisfy the requirements of current special physics experiments. The main reason is the 5 ns time precision restricts the improvement of the precision for the phase detection of the beam bunches.
文摘To improve the control efficiency of Superconducting Electron Cyclotron Resonance Ion source (SECRAL) forHeavy Ion Research Facility in Lanzhou (HIRFL), a upgrade version of control system for SECRAL system wasdesigned and set up in September 2014. The control software package is developed by Visual C++, which is ableto control and monitor all of the equipment for the SECRAL system with about 130 parameters. The previousanalog powers are discarded and four digital high powers are used newly at high voltage platform, which containtwo stove powers, a bias voltage power, and a sputter power. Moreover, four servo motors are added newly, whichcontain work gas, support gas, bias voltage, and sputter voltage. Reflecting vacuum value picturesquely, we plot agraph of inject vacuum, elicit vacuum, and beam vacuum against time. In order to prevent the misoperation whichmay cause the quench of the superconducting magnet, alarm and interlock-protection functions are added to thesoftware and hardware. Simultaneously, added stretch buttons are able to void accidental on-click that might bringabout serious outcome.
文摘The SFC extraction electrostatic deflection plate is located inside the SFC chamber and it is responsible for theSFC beam extraction. Before the SFC-ES position monitoring system was build, the actual position of the cuttingpole and the high voltage cathode pole cannot be "seen" for beam tuning stuff. So they can only tuning the beam"blindly". This is very dangerous, in case of over adjusting the pole, serious damage may be caused. To avoid thiskind of damage, a route limit monitoring system was built in 2012. Using this system, the beam tuning stuff canget the information whether the cutting pole/the high voltage cathode pole is reaching the route limit. If the polehas reached the limit, there will be alarm information in the GUI interface to inform the beam tuning stuff to stopthe motor and change the moving direction. Although this can prevent big damage, precision position detectionfunction cannot be reached, and the SFC extraction electrostatic deflection plate still should be pulled out to checkthe position manually.
文摘High Intensity Heavy-ion Accelerator Facility(HIAF)is a very complex and huge system which is under construction by the Institute of Modern Physics in Huizhou.In order to realize the safe and reliable operation of this facility.
文摘DR(Dielectronic Recombination)and CSRe cluster internal target are two of the important experiment terminals in HIRFL(Heavy Ion Research Facility in Lanzhou).Both terminals have moving detectors,which need to be pushed in or pulled out remotely.Since the old control system has lot of inconvenience such as the decline of control accuracy and running instability,a set of new motion control system is design and realized in 2018.
文摘To establish the sputter ion pump remote control system for TR5 and TR6 of HIRFL(Heavy Ion Research Facility in Lanzhou),EPICS(Experimental Physics And Industrial Control System)is adopted to development new control system.Beckhoff PLC and self-designed hardware module have been used to build the hardware platform and the whole system structure is established based on field bus and EtherCAT(Ethernet for Control Automation Technology)technology.EtherCAT is an ideal Ethernet solution for industrial automation,characterized by outstanding performance and particularly simple handling.In the realization process of the system,IOC record device support and PV definition are achieved.At the same time,we have developed a client application in the CSS environment.In this sputter ion pump control system,we realized the basic interlocking protection function in both of hardware and software.The photo of hardware module is shown in Fig.1.The GUI interface is shown in Fig.2.The control system has being stably run since installed in Aug.2017.
文摘To improve the control efficiency of Ion source for HIRFL,upgrade versions of control systems for ECR and SECRAL were designed and set up in August 2017.The control software packages were developed by Visual C++platform.The control softwares were designed as independent classes.Thus,new devices can be easily added.The control systems were completed and became operational in September 2017.The developed systems have been used successfully for providing various types of beams for physical experiments.
文摘For personal protection purposes,the slow control group designed a radiation dose monitor system and a gate controller with the radiation protection group in HIRFL-CSR.These two works are listed one by one in this article.1.The radiation dose monitor system For radiation protection purposes,the environment radiation dose monitoring is important.According to the characteristics of the detector,self-designed hardware module and switch have been used to build the hardware platform and the whole monitoring system structure is established base on field bus and Ethernet technology.
文摘In motion control area,safety consideration while the moving part touches the limit switch is very important.Otherwise there might be device damage if the moving parts still move toward the limit switch after it touches the switch.In the SFC extraction electrostatic spectrum motion control project[1]and the Xi’an 200 MeV proton device electrostatic spectrum motion control work,we realized the limit position protection function using Phoenix PLC and Rockwell Allen Bradley(AB)PLC.In the Phoenix PLC,a function block is designed using ST language.In the AB PLC,ladder logic programming language is used to realize the function.
基金National Nature Science Foundation of China under Grant No.U1632141 and Western Light Foundation of Chinese Academy of Science under Grant No.29Y926040.
文摘Background Ion pump control system of HIRFL is designed based on the real-time distributed control software,EPICS.The hardware architecture,communication principle,database design and interlock design are introduced and elaborated in the paper.Methods PLC has been adopted to realize functions such as control monitoring and data communication.Interlock protect ion has been designed for ion pump control system to prevent damaging from high voltage.Results The test results show that the system has fast response function and high-speed data processing during the beam running and tuning.The response time of the system could reach 100 ms,the rate of data acquisition reaches to 10 time/s and the interlock protection time less than 40 ms.Conclusion The reliable and stable long-term operation of the vacuum system indicates that the performance has been constantly improved with the continuous optimization of the ion pump control system.