期刊文献+
共找到7篇文章
< 1 >
每页显示 20 50 100
Method of Mechanical Fault Intelligent Diagnosis Based on Vibration Signal of High Voltage Circuit Breaker 被引量:1
1
作者 YANG Zhuangzhuang LIU Yang +3 位作者 ZHOU Guoming LIN Xin JI Tian LI Bin 《高压电器》 CAS CSCD 北大核心 2014年第4期1-6,共6页
Based on vibration signal of high voltage circuit breaker,a new method of intelligent fault diagnosis that wavelet packet extracts energy entropy which are used as characteristic vector of the support vector machine(S... Based on vibration signal of high voltage circuit breaker,a new method of intelligent fault diagnosis that wavelet packet extracts energy entropy which are used as characteristic vector of the support vector machine(SVM)to construct classifier for fault diagnosis is presented.The acceleration sensors are applied to collecting the vibration data of different states of high voltage circuit breakers based on self-made experimental platform in this method.The wavelet packet are fully applied to analyze the vibration signal and decompose vibration signal into three layers,and wavelet packet energy entropy of each frequency band are as the characteristic vector of circuit breaker failure mode.Then the intelligent diagnosis network is established on the basis of the support vector machine theory.It is verified that the method has a better capability of classification and a higher accuracy compared with the traditional neural network diagnosis method through distinguishing the three fault modes which are tripping device stuck,the vacuum arcing chamber fixed bolt looseness and too much friction force of the transmission mechanism of circuit breaker in this paper. 展开更多
关键词 SVM energy entropy high voltage circuit breaker intelligent diagnosis
下载PDF
Analysis of multiple-faults of high-voltage circuit breakers based on non-negative matrix decomposition
2
作者 Yongrong Zhou Zhaoxing Ma +1 位作者 Hao Chen Ruihua Wang 《Global Energy Interconnection》 EI CSCD 2024年第2期179-189,共11页
High-voltage circuit breakers are the core equipment in power networks,and to a certain extent,are related to the safe and reliable operation of power systems.However,their core components are prone to mechanical faul... High-voltage circuit breakers are the core equipment in power networks,and to a certain extent,are related to the safe and reliable operation of power systems.However,their core components are prone to mechanical faults.This study proposes a component separation method to detect multiple mechanical faults in circuit breakers that can achieve online real-time monitoring.First,a model and strategy are presented for obtaining mechanical voiceprint signals from circuit breakers.Subsequently,the component separation method was used to decompose the voiceprint signals of multiple faults into individual component signals.Based on this,the recognition of the features of a single-fault voiceprint signal can be achieved.Finally,multiple faults in high-voltage circuit breakers were identified through an experimental simulation and verification of the circuit breaker voiceprint signals collected from the substation site.The research results indicate that the proposed method exhibits excellent performance for multiple mechanical faults,such as spring structures and loose internal components of circuit breakers.In addition,it provides a reference method for the real-time online monitoring of high-voltage circuit breakers. 展开更多
关键词 high voltage circuit breaker Signal separation MONITOR Multiple faults Power system
下载PDF
Study on the Mathematical Model of Dielectric Recovery Characteristics in High Voltage SF6 Circuit Breaker 被引量:13
3
作者 林莘 王飞鸣 +2 位作者 徐建源 夏亚龙 刘卫东 《Plasma Science and Technology》 SCIE EI CAS CSCD 2016年第3期223-229,共7页
According to the stream theory, this paper proposes a mathematical model of the dielectric recovery characteristic based on the two-temperature ionization equilibrium equation. Taking the dynamic variation of charged ... According to the stream theory, this paper proposes a mathematical model of the dielectric recovery characteristic based on the two-temperature ionization equilibrium equation. Taking the dynamic variation of charged particle's ionization and attachment into account, this model can be used in collaboration with the Coulomb collision model, which gives the relationship of the heavy particle temperature and electron temperature to calculate the electron density and temperature under different pressure and electric field conditions, so as to deliver the breakdown electric field strength under different pressure conditions. Meanwhile an experiment loop of the circuit breaker has been built to measure the breakdown voltage. It is shown that calculated results are in conformity with experiment results on the whole while results based on the stream criterion are larger than experiment results. This indicates that the mathematical model proposed here is more accurate for calculating the dielectric recovery characteristic, it is derived from the stream model with some improvement and refinement and has great significance for increasing the simulation accuracy of circuit breaker's interruption characteristic. 展开更多
关键词 SF6 high voltage circuit breaker dielectric recovery characteristic the break-down voltage experiment of dynamic breakdown Saha ionization equilibrium
下载PDF
Multi-mapping Fault Diagnosis of High Voltage Circuit Breaker Based on Mathematical Morphology and Wavelet Entropy 被引量:5
4
作者 Tianyao Ji Lin Yi +2 位作者 Wenhu Tang Mengjie Shi Q.H.Wu 《CSEE Journal of Power and Energy Systems》 SCIE CSCD 2019年第1期130-138,共9页
Mechanical faults of high voltage circuit breakers(CBs)seriously affect the reliability of their operation,which may cause severe damage to power systems.In order to monitor operational conditions and detect mechanica... Mechanical faults of high voltage circuit breakers(CBs)seriously affect the reliability of their operation,which may cause severe damage to power systems.In order to monitor operational conditions and detect mechanical faults of CBs,a multi-parameter monitoring system is designed and a fault diagnosis method based on multi-mapping is proposed.The paper focuses on the trip/close circuits,the spring-charging mechanism and the transmission mechanism,and obtains four current signals and a vibration signal that can reflect CB conditions.For the current signals,a morphological filter is used to remove noise and then characteristics of the waveforms’shape information are extracted.For vibration signals,the wavelet packet transform is used to decompose the signal into various frequency bands,and the sample entropy of the low frequency bands and the wavelet energy of the high frequency bands are calculated,respectively.Based on these feature parameters,a multi-mapping strategy is proposed for CB fault diagnosis.Laboratory experiments have been conducted to obtain on-site signals under various conditions,and experiment results have verified that monitoring the aforementioned signals and using the corresponding feature extraction and fault diagnosis methods,the mechanical faults of high voltage CBs can be effectively diagnosed. 展开更多
关键词 Fault diagnosis high voltage circuit breaker multi-mapping sample entropy wavelet energy
原文传递
Research on Online Monitoring Methods on SF_(6) Circuit Breakers
5
作者 CHENG Tingting GAO Wensheng ZHAO Yuming 《高压电器》 CAS CSCD 北大核心 2019年第3期1-7,14,共8页
To promote the accuracy and application of arcing time measurement for SF_6 circuit breaker in substation,five measurement methods are investigated by two cases experimentally. First,the test results of the five metho... To promote the accuracy and application of arcing time measurement for SF_6 circuit breaker in substation,five measurement methods are investigated by two cases experimentally. First,the test results of the five methods for a circuit breaker in different stages of wear and a circuit breaker with a component failure were presented. Then,the time error is analyzed by simulation.Finally,the advantage and disadvantage of these methods are discussed. 展开更多
关键词 circuit breaker high voltage circuit breaker arcing time arc duration online monitoring wavelet analysis
下载PDF
Circuit Model with Current Interruption for Hybrid High Voltage DC Circuit Breakers to Achieve Precise Current Experiments
6
作者 Zhonghao Dongye Lei Qi +2 位作者 Bing Ji Xiaoguang Wei Xiang Cui 《CSEE Journal of Power and Energy Systems》 SCIE EI CSCD 2022年第4期1250-1260,共11页
The current interruption test based on an LC resonance circuit for hybrid DC circuit breakers(HVDC CBs)is widely employed to characterize the current interruption capability of CBs.In order to ensure a high-fidelity r... The current interruption test based on an LC resonance circuit for hybrid DC circuit breakers(HVDC CBs)is widely employed to characterize the current interruption capability of CBs.In order to ensure a high-fidelity replica of the fault current in a high voltage application,this paper first proposes an equivalent model of the test circuit,where not only parasitic resistances but also the threshold voltages and on-state resistances of various semiconductor devices are considered.Moreover,the analytical formula of the test current is derived by including the working principle of the HVDC CB.Secondly,the parameter extraction method,which combines finite element analysis and measurements by an impedance analyzer,is given in this paper.The extracted result implies that,in current interruption transients,equivalent resistances of 500 kV CB are as large as 535 mS,which have a significant influence on current waveforms.Thirdly,the 34 kV/25 kA current interruption test for the 500 kV CB is conducted.The measured results are proved to be consistent with the analytical results obtained from the proposed model,and the relative error is less than 2%. 展开更多
关键词 Current interruption test high voltage DC circuit breaker
原文传递
Research of Arc Chamber Optimization Techniques Based on Flow Field and Arc Joint Simulation 被引量:1
7
作者 钟建英 郭煜敬 张豪 《Plasma Science and Technology》 SCIE EI CAS CSCD 2016年第3期319-324,共6页
The preliminary design of an arc chamber in the 550 kV SF6 circuit breaker was proposed in accordance with the technicai requirements and design experience. The structural optimization was carried out according to the... The preliminary design of an arc chamber in the 550 kV SF6 circuit breaker was proposed in accordance with the technicai requirements and design experience. The structural optimization was carried out according to the no-load flow field simulation results and verified by no-load pressure measurement. Based on load simulation results such as temperature field variation at the arc area and the tendency of post arc current under different recovery voltage, the second optimal design was completed and its correctness was certificated by a breaking test. Results demonstrate that the interrupting capacity of an arc chamber can be evaluated by the comparison of the gas medium recovery speed and post arc current growth rate. 展开更多
关键词 flow filed ARC SIMULATION high voltage SF6 circuit breaker post arc current
下载PDF
上一页 1 下一页 到第