期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
Comparison between open phase fault of arc suppression coil and single phase to earth fault in coal mine distribution network 被引量:3
1
作者 LI Xiao-bo WANG Chong-lin 《Journal of China University of Mining and Technology》 EI 2008年第3期368-372,共5页
When, in a coal mine distribution network whose neutral point is grounded by an arc suppression coil (ASC), a fault occurs in the ASC, compensation cannot be properly realized. Furthermore, it can damage the safe and ... When, in a coal mine distribution network whose neutral point is grounded by an arc suppression coil (ASC), a fault occurs in the ASC, compensation cannot be properly realized. Furthermore, it can damage the safe and reliable run of the network. We first introduce a three-phase five-column arc suppression coil (TPFCASC) and discuss its autotracking compensation theory. Then we compare the single phase to ground fault of the coal mine distribution network with an open phase fault at the TPFCASC using the Thévenin theory, the symmetrical-component method and the complex sequence network respectively. The results show that, in both types of faults, zero-sequence voltage of the network will appear and the maximum magnitude of this zero-sequence voltage is different in both faults. Based on this situation, a protection for the open phase fault at the TPFCASC should be estab-lished. 展开更多
关键词 open phase PROTECTION single phase to ground fault three-phase five-column arc suppression coil (TPFCASC)
下载PDF
上一页 1 下一页 到第
使用帮助 返回顶部