Structure of main air discharging switch and a crowbar TVS (triggered vacuum switch) are designed and their triggering characteristics are investigated. The experimental results showed that for TVS the operating vol...Structure of main air discharging switch and a crowbar TVS (triggered vacuum switch) are designed and their triggering characteristics are investigated. The experimental results showed that for TVS the operating voltage range is from 1.3 kV to 120 kV, its maximum delay time is 400 ns and its jitter is 4-10 ns. Based on these results the crowbar 10/350μs (i.e., with a front time of 10μs and a duration of 350 μs) pulse current circuit and its controlling circuit are designed. With a 10μF stored capacitor C and a 6 μF waveform forming induction, a pulse current is generated with a maximum of 100 kA, front time of 10 ns and duration of 350μs. This pulse waveform can be used for testing SPD (surge protective devices).展开更多
基金supported by the New Century Talent Foundation of Ministry of Education of China (NCET-08-0438)
文摘Structure of main air discharging switch and a crowbar TVS (triggered vacuum switch) are designed and their triggering characteristics are investigated. The experimental results showed that for TVS the operating voltage range is from 1.3 kV to 120 kV, its maximum delay time is 400 ns and its jitter is 4-10 ns. Based on these results the crowbar 10/350μs (i.e., with a front time of 10μs and a duration of 350 μs) pulse current circuit and its controlling circuit are designed. With a 10μF stored capacitor C and a 6 μF waveform forming induction, a pulse current is generated with a maximum of 100 kA, front time of 10 ns and duration of 350μs. This pulse waveform can be used for testing SPD (surge protective devices).