Half-wavelength AC transmission(HWACT) is an ultra-long distance AC transmission technology, whose electrical distance is close to half-wavelength at the system power frequency. It is very important for the constructi...Half-wavelength AC transmission(HWACT) is an ultra-long distance AC transmission technology, whose electrical distance is close to half-wavelength at the system power frequency. It is very important for the construction and operation of HWACT to analyze its fault features and corresponding protection technology. In this paper, the steady-state voltage and current characteristics of the bus bar and fault point and the steady-state overvoltage distribution along the line will be analyzed when a three-phase symmetrical short-circuit fault occurs on an HWACT line. On this basis, the threephase fault characteristics for longer transmission lines are also studied.展开更多
In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the curren...In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the current at power frequency(50 Hz), power frequency combining the 11 th harmonic and power frequency combining the 24 th harmonic show that the high-order harmonic current would lead to higher decreasing rate of current before current-zero period. In addition, the influence of arc on the amplitude of high-order harmonic current is not negligible. Thus, the coupling of arc with AC filter branch circuit is quite necessary in the numerical modeling of the circuit breaker in the AC filter branch at the high voltage direct current converter station.展开更多
A novel method for detecting early damage at the steel-concrete interface due to external loading based on AC impedance spectroscopy technology was proposed.Firstly,alkali pretreatment was introduced to ensure the acc...A novel method for detecting early damage at the steel-concrete interface due to external loading based on AC impedance spectroscopy technology was proposed.Firstly,alkali pretreatment was introduced to ensure the accuracy and repeatability of the AC impedance test.Secondly,the AC impedance spectroscopy between the steel bar and concrete surface of different bonding positions was tested,and then the physical quantities reflecting the bonding damage condition were obtained by equivalent circuit fitting.Theoretical debonding position calculation and AC conductive structure analysis indicate that the change of interface resistance and interface capacitance can seize the development of bonding damage during the loading process.As the interface damage develops,obvious changes in interface resistance and interface capacitance are observed,and they cannot be recovered after unloading.展开更多
This report shows how starting from classic electric circuits embodying commonly electric components we have reached semi-complicated circuits embodying the same components that analyzing the signal characteristics re...This report shows how starting from classic electric circuits embodying commonly electric components we have reached semi-complicated circuits embodying the same components that analyzing the signal characteristics requires a Computer Algebra System. Our approach distinguishes itself from the electrical engineers’ (EE) approach that relies on utilizing commercially available software. Our approach step-by-step shows how Kirchhoff’s rules are applied conducive to the needed circuit information. It is shown for the case at hand the characteristic information is a set of coupled differential equations and that with the help of Mathematica numeric solutions are sought. Our report paves the research road for unlimited creative similar circuits with any degree of complications. Occasionally, by tweaking the circuits we have addressed the “what if” scenarios widening the scope of the investigation. Justification of the accuracy of our analysis for the generalized circuits is cross-checked by arranging the components symmetrizing the circuit leading to an intuitively predictable reasonable result. Mathematica codes are embedded assisting the interested reader in producing and extending our results.展开更多
With rapid growth of power demand, transmission capacity is also in urgent need of upgrading. In some cases, converting existing AC transmission lines to DC lines can Improve the transmission capacity and reduce the c...With rapid growth of power demand, transmission capacity is also in urgent need of upgrading. In some cases, converting existing AC transmission lines to DC lines can Improve the transmission capacity and reduce the construction investment. In this paper, the upstream finite element method was expanded to calculate the total electric field of same tower multi-circuit DC lines converted from double-circuit AC lines, and the validity of the algorithm was confirmed by experiments. Taking a DC line converted from a typical same tower 500 kV double-circuit AC transmission line as an example, the surface electric field and the ground total electric field in different pole conductor arrangement schemes were calculated and analyzed, and the critical height of pole conductors for DC lines in residential and non-residential area were determined. Then, the corridor width of DC and AC lines at critical height in residential and non-residential areas before and after AC-DC line transformation were compared. The results indicate that for DC lines converted from common 500 kV double-circuit AC lines, the ground total electric field can meet the requirements of corresponding standard with appropriate pole conductor arrangement schemes.展开更多
为在实验室环境下实现40 k W容量的船舶中压电力模拟试验系统,需要将380 V发电机组输出的交流电经电力变换得到稳定的4 k V直流输出。系统采用两级变换,前级AC/DC变换采用无桥boost型PFC(Power Factor Correction)电路,后级DC/DC变换采...为在实验室环境下实现40 k W容量的船舶中压电力模拟试验系统,需要将380 V发电机组输出的交流电经电力变换得到稳定的4 k V直流输出。系统采用两级变换,前级AC/DC变换采用无桥boost型PFC(Power Factor Correction)电路,后级DC/DC变换采用四路全桥PWM(Pulse Width Modulation)变换器级联进行升压,其中一路为移相全桥完成调压控制输出,三路为普通全桥得到固定电压输出。在MATLAB/Simulink环境下对该AC/DC变换器系统进行了系统建模,仿真结果表明,该方案能输出稳定的4 k V电压,效率94.8%,纹波2.08%。展开更多
基金supported by National Key Research and Development Program of China(2016YFB0900100)
文摘Half-wavelength AC transmission(HWACT) is an ultra-long distance AC transmission technology, whose electrical distance is close to half-wavelength at the system power frequency. It is very important for the construction and operation of HWACT to analyze its fault features and corresponding protection technology. In this paper, the steady-state voltage and current characteristics of the bus bar and fault point and the steady-state overvoltage distribution along the line will be analyzed when a three-phase symmetrical short-circuit fault occurs on an HWACT line. On this basis, the threephase fault characteristics for longer transmission lines are also studied.
基金supported by the Major Science and Technology Project of China Southern Power Grid Co.,Ltd(ZBKJXM20170065):Research on Harmonic Resonance Mechanism,Suppression Measures and Impact on Main Equipment of AC/DC Hybrid Power Grid。
文摘In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the current at power frequency(50 Hz), power frequency combining the 11 th harmonic and power frequency combining the 24 th harmonic show that the high-order harmonic current would lead to higher decreasing rate of current before current-zero period. In addition, the influence of arc on the amplitude of high-order harmonic current is not negligible. Thus, the coupling of arc with AC filter branch circuit is quite necessary in the numerical modeling of the circuit breaker in the AC filter branch at the high voltage direct current converter station.
基金Funded by the Opening Funds of State Key Laboratory of Building Safety and Built Environment and National Engineering Research Center of Building Technology (No.BSBE2019-07)the Young Talent Support Program of Hebei Institutions of Higher Learning (No.BJ2017019)the National Natural Science Foundation of China (No.51808357)。
文摘A novel method for detecting early damage at the steel-concrete interface due to external loading based on AC impedance spectroscopy technology was proposed.Firstly,alkali pretreatment was introduced to ensure the accuracy and repeatability of the AC impedance test.Secondly,the AC impedance spectroscopy between the steel bar and concrete surface of different bonding positions was tested,and then the physical quantities reflecting the bonding damage condition were obtained by equivalent circuit fitting.Theoretical debonding position calculation and AC conductive structure analysis indicate that the change of interface resistance and interface capacitance can seize the development of bonding damage during the loading process.As the interface damage develops,obvious changes in interface resistance and interface capacitance are observed,and they cannot be recovered after unloading.
文摘This report shows how starting from classic electric circuits embodying commonly electric components we have reached semi-complicated circuits embodying the same components that analyzing the signal characteristics requires a Computer Algebra System. Our approach distinguishes itself from the electrical engineers’ (EE) approach that relies on utilizing commercially available software. Our approach step-by-step shows how Kirchhoff’s rules are applied conducive to the needed circuit information. It is shown for the case at hand the characteristic information is a set of coupled differential equations and that with the help of Mathematica numeric solutions are sought. Our report paves the research road for unlimited creative similar circuits with any degree of complications. Occasionally, by tweaking the circuits we have addressed the “what if” scenarios widening the scope of the investigation. Justification of the accuracy of our analysis for the generalized circuits is cross-checked by arranging the components symmetrizing the circuit leading to an intuitively predictable reasonable result. Mathematica codes are embedded assisting the interested reader in producing and extending our results.
文摘With rapid growth of power demand, transmission capacity is also in urgent need of upgrading. In some cases, converting existing AC transmission lines to DC lines can Improve the transmission capacity and reduce the construction investment. In this paper, the upstream finite element method was expanded to calculate the total electric field of same tower multi-circuit DC lines converted from double-circuit AC lines, and the validity of the algorithm was confirmed by experiments. Taking a DC line converted from a typical same tower 500 kV double-circuit AC transmission line as an example, the surface electric field and the ground total electric field in different pole conductor arrangement schemes were calculated and analyzed, and the critical height of pole conductors for DC lines in residential and non-residential area were determined. Then, the corridor width of DC and AC lines at critical height in residential and non-residential areas before and after AC-DC line transformation were compared. The results indicate that for DC lines converted from common 500 kV double-circuit AC lines, the ground total electric field can meet the requirements of corresponding standard with appropriate pole conductor arrangement schemes.
文摘为在实验室环境下实现40 k W容量的船舶中压电力模拟试验系统,需要将380 V发电机组输出的交流电经电力变换得到稳定的4 k V直流输出。系统采用两级变换,前级AC/DC变换采用无桥boost型PFC(Power Factor Correction)电路,后级DC/DC变换采用四路全桥PWM(Pulse Width Modulation)变换器级联进行升压,其中一路为移相全桥完成调压控制输出,三路为普通全桥得到固定电压输出。在MATLAB/Simulink环境下对该AC/DC变换器系统进行了系统建模,仿真结果表明,该方案能输出稳定的4 k V电压,效率94.8%,纹波2.08%。