The acoustic emission (AE) method could be used to detect and locate partial discharges (PD) in cast-resin dry-type transformers.However,due to the high sound attenuation in the filled epoxy,the signal is prone to int...The acoustic emission (AE) method could be used to detect and locate partial discharges (PD) in cast-resin dry-type transformers.However,due to the high sound attenuation in the filled epoxy,the signal is prone to interference from external noises and thus,in practice,there is little possibility of detecting PD.In this study,two techniques were developed to alleviate the shortcomings of the AE method.First,a waveguide is installed on the high-voltage (HV) windings,so that the acoustic signals of PD will propagate to the AE sensors that are installed on both terminals of the waveguide.The location of the winding that has PD can then be detected from the difference in arrival time of the acoustic signals.Test results indicate that the waveguide technique is able to enhance the safety of a measurement system and offers the advantages of easy installation and higher flexibility.Second,a specially designed AE sensor pair is used to distinguish whether acoustic signals are generated by PD inside the HV winding or by the corona outside the transformers.Using these two techniques of waveguide and AE sensor pair not only greatly improves sensitivity but also increases the reliability of the measurement system.Practical test results show that the new techniques can be used to locate precisely the PD in HV windings.展开更多
基金supported by the National Science Council,Taiwan (No.NSC 92-2622-E-006-142)the Program of Top 100 Universities Advancement,Ministry of Education,Taiwan
文摘The acoustic emission (AE) method could be used to detect and locate partial discharges (PD) in cast-resin dry-type transformers.However,due to the high sound attenuation in the filled epoxy,the signal is prone to interference from external noises and thus,in practice,there is little possibility of detecting PD.In this study,two techniques were developed to alleviate the shortcomings of the AE method.First,a waveguide is installed on the high-voltage (HV) windings,so that the acoustic signals of PD will propagate to the AE sensors that are installed on both terminals of the waveguide.The location of the winding that has PD can then be detected from the difference in arrival time of the acoustic signals.Test results indicate that the waveguide technique is able to enhance the safety of a measurement system and offers the advantages of easy installation and higher flexibility.Second,a specially designed AE sensor pair is used to distinguish whether acoustic signals are generated by PD inside the HV winding or by the corona outside the transformers.Using these two techniques of waveguide and AE sensor pair not only greatly improves sensitivity but also increases the reliability of the measurement system.Practical test results show that the new techniques can be used to locate precisely the PD in HV windings.