It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution.Features of double sided elimination method were illustrated.Quantitative calculation of sing...It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution.Features of double sided elimination method were illustrated.Quantitative calculation of single-phase earth fault current distribution and case verification were accomplished by using the loop method.Influences of some factors,such as single-phase earth fault location and ground resistance of poles,on short-circuit current distribution were discussed.Results show that:1) results of the loop method conform to those of double sided elimination method;2) the fault location hardly influences macro-distribution of short-circuit current.However,current near fault location is evidently influenced;and 3) the short-circuit current distribution is not so sensitive to the ground resistance of poles.展开更多
There are two major protective methods against lightning outages on overhead distribution lines.One is a surge arrester,and the other is an overhead ground wire.The surge arresters have rather constant effect regardle...There are two major protective methods against lightning outages on overhead distribution lines.One is a surge arrester,and the other is an overhead ground wire.The surge arresters have rather constant effect regardless of the cause of the lightning outage.On the other hand,the effect of an overhead ground wire is quite different in two major causes,the direct lightning hit and the induced overvoltage.It is sufficient to provide surge arresters with an interval of 300 m for protection against the induced overvoltage caused by the nearby lightning stroke.Use of an overhead ground wire together with surge arresters is effective for lightning protection against the direct lightning hit to a distribution line.Puncture of surge arresters is the popular outage when the outage caused by the insulation break decreases sufficiently.Also,the existence of nearby trees leads to the line break due to the side flash from a tree.Advanced lightning protection equipment with ZnO arrester components is popular in Japan.Modeling of a pole transformer and application of an electromagnetic analysis method,such as FDTD method,to surge phenomena is considerably advanced.展开更多
文摘It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution.Features of double sided elimination method were illustrated.Quantitative calculation of single-phase earth fault current distribution and case verification were accomplished by using the loop method.Influences of some factors,such as single-phase earth fault location and ground resistance of poles,on short-circuit current distribution were discussed.Results show that:1) results of the loop method conform to those of double sided elimination method;2) the fault location hardly influences macro-distribution of short-circuit current.However,current near fault location is evidently influenced;and 3) the short-circuit current distribution is not so sensitive to the ground resistance of poles.
文摘There are two major protective methods against lightning outages on overhead distribution lines.One is a surge arrester,and the other is an overhead ground wire.The surge arresters have rather constant effect regardless of the cause of the lightning outage.On the other hand,the effect of an overhead ground wire is quite different in two major causes,the direct lightning hit and the induced overvoltage.It is sufficient to provide surge arresters with an interval of 300 m for protection against the induced overvoltage caused by the nearby lightning stroke.Use of an overhead ground wire together with surge arresters is effective for lightning protection against the direct lightning hit to a distribution line.Puncture of surge arresters is the popular outage when the outage caused by the insulation break decreases sufficiently.Also,the existence of nearby trees leads to the line break due to the side flash from a tree.Advanced lightning protection equipment with ZnO arrester components is popular in Japan.Modeling of a pole transformer and application of an electromagnetic analysis method,such as FDTD method,to surge phenomena is considerably advanced.