Several large-scale wind turbine tripping accidents occurred in Jiuquan wind power base in 2011.According to the on-site survey and analysis of these accidents related to relay protection,causes were found to be the c...Several large-scale wind turbine tripping accidents occurred in Jiuquan wind power base in 2011.According to the on-site survey and analysis of these accidents related to relay protection,causes were found to be the collection system defects and low correct operation rate of small current grounded line selectors of the unearthed neutral point collection system.By referring to both the characteristics of Jiuquan wind power base and arrangement of relay protection,the short-circuit features of wind power and its impacts on relay protection are analyzed.The collection system and the retrofit of the small current grounded line selector are improved by specific countermeasures.Finally,further research subjects are put forward.展开更多
A novel operation control method for relay protection in flexible DC distribution networks with distributed power supply is proposed to address the issue of inaccurate fault location during relay protection,leading to...A novel operation control method for relay protection in flexible DC distribution networks with distributed power supply is proposed to address the issue of inaccurate fault location during relay protection,leading to poor performance.The method combines a fault-tolerant fault location method based on long-term and short-term memory networks to accurately locate the fault section.Then,an operation control method for relay protection based on adaptive weight and whale optimization algorithm(WOA)is used to construct an objective function considering the shortest relay protection action time and the smallest impulse current.The adaptive weight and WOA are employed to obtain the optimal strategy for relay protection operation control,reducing the action time and impulse current.Experimental results demonstrate the effectiveness of the proposed method in accurately locating faults and improving relay protection performance.The longest operation time is reduced by 4.7023 s,and the maximum impulse current is limited to 0.3 A,effectively controlling the impact of large impulse currents and enhancing control efficiency.展开更多
The intelligent substation relay protection facility is a fundamental element in construction of modern power system,based on the principles of flexibility,security and accuracy,and it can be divided into process laye...The intelligent substation relay protection facility is a fundamental element in construction of modern power system,based on the principles of flexibility,security and accuracy,and it can be divided into process layer and substation layer according to specific equipment.The former is suitable for individual sampling of disposable equipment,can be separated from the base station synchronization sampling,with the help of synchronous digital system and ping-pong algorithm to achieve synchronization of the overall sampling,that is to take the distribution protection components,through the separate transmission medium to realize the information transmission;the latter is for variable power plant components centralized backup protection,taking online real-time tuning technique.展开更多
The article discusses the possibility of further modernization of the standard microprocessor relay protection of AC overhead system feeders DPA-27.5-TNF, which is operated on the Trans-Baikal Railway by creating an a...The article discusses the possibility of further modernization of the standard microprocessor relay protection of AC overhead system feeders DPA-27.5-TNF, which is operated on the Trans-Baikal Railway by creating an additional automated system of unified templates necessary for the occurrence of “trainability” elements. The templates will be formed via a separate dedicated channel for transmission, processing and storage of the necessary information, not related to the operation of the terminal, with its subsequent visualization at the workplace of the duty personnel of traction substations, together with information from the “GID” software received via another dedicated wired channel. With the help of such a base of unified preset templates, in the future, it will be possible not only to identify the specific causes of each emergency shutdown but also to reduce their number by dynamically adjusting the existing presets of the standard operation algorithm.展开更多
With the development of large-scale complicated modern power systems, the requirement for the associated protection scheme tends to be more stringent and its combination more complex. However, it is very difficult to ...With the development of large-scale complicated modern power systems, the requirement for the associated protection scheme tends to be more stringent and its combination more complex. However, it is very difficult to figure out the factors of failure of such systems. This paper proposes a Petri net model of a transmission line protection relaying system, including three types of relays as well as an automatic reclosing device, and shows how to diagnose serial failure of the system by analyzing invariant sets of the model. Furthermore, it gives four basic types of failure sequences and its execution is much more intuitive and effective than the traditional method.展开更多
The research and development of ultra high speed protective relay of transmission line has got great interest and attention of protective relay engineer over the world. Several versions and schemes of ultra high speed...The research and development of ultra high speed protective relay of transmission line has got great interest and attention of protective relay engineer over the world. Several versions and schemes of ultra high speed relay have been studied and designed in recent twenty years. But only a few of them have got actual apiication in the power system. The relay based on the deviation of power frequency component (DPFC) can get very high reliability with ultra high speed so it has got wide application in Chinese power system. Thousands relay sets have been applied and its operation experience verifies their excellent performance. This paper summarizes the course of the development of the uItra high speed protective relay and compares the merits and defects of the main schemes which have been developed. The principle and successful pratice of the ultra high speed protection based on DPFC reIay are introduced.展开更多
This paper presents the existing state anddevelopment planning of East China PowerSystem, which refers to load, power source,power network, system protection, dispatchautomation and system communication.
The article discusses the possibility of a potential reduction in the number of operations of microprocessor relay protection of feeders of the contact network of AC railways TsZA-27.5-FKS (FTS) for unknown reasons. R...The article discusses the possibility of a potential reduction in the number of operations of microprocessor relay protection of feeders of the contact network of AC railways TsZA-27.5-FKS (FTS) for unknown reasons. Real statistics on the number of microprocessor relay protection operations at the Buryatskaya traction substation are presented, simulation of the real train situation (in accordance with the regime maps of the throughput capacity of the sections of the Trans-Baikal railway) was carried out in the specialized software complex “KORTES”. Based on the results of the analysis of simulation modeling, the process of forming a unified template of settings using neural network technologies is considered, which characterizes only this specific regular train situation. To protect objects in the event of pre-emergency and emergency modes of operation of the traction power supply system, a variant of changing the standard operation algorithm of the TsZA-27.5-FKS (FTS) terminal by introducing additional blocks for calculating the predictive functions of current and voltage has been proposed.展开更多
As the smart grid concepts are emphasized lately, the need to modernize the power engineering education is also well recognized. This paper presents a set of newly developed modeling, simulation and testing tools aime...As the smart grid concepts are emphasized lately, the need to modernize the power engineering education is also well recognized. This paper presents a set of newly developed modeling, simulation and testing tools aimed at better understanding of the design concept and related applications for protective relaying and substation automation solutions for the smart grid. Since the smart grid applications require integration of data from multiple IEDs (intelligent electronic devices), understanding properties of each IED type in detail, as well as their responses to the power system events is needed. In addition, understanding the communication requirements to perform data integration is also important. To illustrate how the mentioned smart grid issues may be taught, the following advanced teaching approaches are presented: (1) Use of modeling and simulation means to better understand interaction between the relays and power system; (2) Use of IED test facilities to better understand performance of physical devices used for protection, monitoring and control; (3) Utilization of communication network modeling tools to simulate the communication network within SAS (substation automation system). Examples showing the use of proposed techniques for teaching the fundamentals and applications are presented. The examples demonstrate the adequacy and efficiency of the proposed techniques.展开更多
As the false trips of remote protection relays are among the main reasons behind cascading blackouts, it is critical to design reliable relay protection. Even though common protection schemes on traditional power syst...As the false trips of remote protection relays are among the main reasons behind cascading blackouts, it is critical to design reliable relay protection. Even though common protection schemes on traditional power systems have been investigated for a few decades, cascading failures in recent years indicate more research needed in this area. Consequently, researchers have proposed agent-based methods on the Smart Grid (SG) to address this issue. However, these existing agent-based methods simply use TCP protocol without considering real-time communication requirements (such as bandwidth and delay). To deal with this issue, several methods for efficient network resource management are proposed. Furthermore, these existing methods do not consider the potential issues in practical communication networks, which may result in delay violation and trigger relay false trips. We have discussed simple backup solutions in the previous work. In this paper, in addition to network efficiency, we focus on improving the system reliability by exploring known power system information and minimizing the chances of false trips of important remote relays, e.g., defining power line priorities based on their importance. Moreover, to further improve the. system reliability, we also in- vestigate the peer-to-peer protection approaches to address the single point of failure of centralized control center.展开更多
Quasi-PID control method that is able to effectively inhibit the inherent tracking error of PI control method is proposed on the basis of a rounded theoretical analysis of a model of switching power amplifiers (SPAs)....Quasi-PID control method that is able to effectively inhibit the inherent tracking error of PI control method is proposed on the basis of a rounded theoretical analysis of a model of switching power amplifiers (SPAs). To avoid the harmful impacts of the circuit parameter variations and the random disturbances on quasi-PID control method, a single neuron is introduced to endow it with self-adaptability. Quasi-PID control method and the single neuron combine with each other perfectly, and their formation is named as single-neuron adaptive quasi-PID control method. Simulation and experimental results show that single-neuron adaptive quasi-PID control method can accurately track both the predictable and the unpredictable waveforms. Quantitative analysis demonstrates that the accuracy of single-neuron adaptive quasi-PID control method is comparable to that of linear power amplifiers (LPAs) and so can fulfill the requirements of some high-accuracy applications, such as protective relay test. Such accuracy is very difficult to be achieved by many modern control methods for converter controls. Compared with other modern control methods, the programming realization of single-neuron adaptive quasi-PID control method is more suitable for real-time applications and realization on low-end microprocessors for its simple structure and lower computational complexity.展开更多
In order to provide a novel and more effective alternative to the commonly used relay protection testing device that outputs only the sinusoidal testing signals, the concept of fault waveform regenerator is proposed i...In order to provide a novel and more effective alternative to the commonly used relay protection testing device that outputs only the sinusoidal testing signals, the concept of fault waveform regenerator is proposed in this paper, together with its hardware structure and software flow chart. Fault waveform regenerator mainly depends on its power amplifiers (PAs) to regenerate the fault waveforms recorded by digital fault recorder (DFR). To counteract the PA’s inherent nonlinear distortions, a digital closed-loop modification technique that is different from the predistortion technique is conceived. And the experimental results verify the effectiveness of the fault waveform regenerator based on the digital closed-loop modification technique.展开更多
The contradiction of the relay protection with other task has been solved by double CPU’s structure in this comprehensive monitor. Thus the speed of the data processing has raised and the requirement of relay protect...The contradiction of the relay protection with other task has been solved by double CPU’s structure in this comprehensive monitor. Thus the speed of the data processing has raised and the requirement of relay protection and the real bine monitoring has all been satisfied. The input precision of the fault current and the rated current has been assured respectively by applying the relay protection CT and measurement CT. The algorithm of FFT with or without the difference has remarkably raised the precision of the protective measurement and removed the influence of the attenuation DC component in the fault current. Thus the accuracy and reliability of the protective trigger has been raised greatly.展开更多
Co-ordination of directional over current relays(DOCR) requires the selection and setting of relays so as to sequentially isolate only that portion of the power system where an abnormality has occurred.The problem of ...Co-ordination of directional over current relays(DOCR) requires the selection and setting of relays so as to sequentially isolate only that portion of the power system where an abnormality has occurred.The problem of coordinating protective relays in electrical power systems consists of selecting suitable settings such that their fundamental protective function is met,given operational requirements of sensitivity,selectivity,reliability and speed.Directional over current relays are best suited for protection of an interconnected sub-station transmission system.One of the major problems associated with this type of protection is the difficulty in coordinating relays.To insure proper coordination,all the main/back up relay pairs must be determined.This paper presents an effective algorithm to determine the minimum number of break points and main/back up relay pairs using relative sequence matrix(RSM).A novel optimization technique based on evolutionary programming was developed using these main/back up relay pairs for directional over current relay coordination in multi-loop networks.Since the problem has multi-optimum points,conventional mathematics based optimization techniques may sometimes fail.Hence evolutionary programming(EP) was used,as it is a stochastic multi-point search optimization algorithm capable of escaping from the local optimum problem,giving a better chance of reaching a global optimum.The method developed was tested on an existing 6 bus,7 line system and better results were obtained than with conventional methods.展开更多
基金supported by National High Technology Research and Development Program of China(863Program)(No.2011AA05A104)
文摘Several large-scale wind turbine tripping accidents occurred in Jiuquan wind power base in 2011.According to the on-site survey and analysis of these accidents related to relay protection,causes were found to be the collection system defects and low correct operation rate of small current grounded line selectors of the unearthed neutral point collection system.By referring to both the characteristics of Jiuquan wind power base and arrangement of relay protection,the short-circuit features of wind power and its impacts on relay protection are analyzed.The collection system and the retrofit of the small current grounded line selector are improved by specific countermeasures.Finally,further research subjects are put forward.
文摘A novel operation control method for relay protection in flexible DC distribution networks with distributed power supply is proposed to address the issue of inaccurate fault location during relay protection,leading to poor performance.The method combines a fault-tolerant fault location method based on long-term and short-term memory networks to accurately locate the fault section.Then,an operation control method for relay protection based on adaptive weight and whale optimization algorithm(WOA)is used to construct an objective function considering the shortest relay protection action time and the smallest impulse current.The adaptive weight and WOA are employed to obtain the optimal strategy for relay protection operation control,reducing the action time and impulse current.Experimental results demonstrate the effectiveness of the proposed method in accurately locating faults and improving relay protection performance.The longest operation time is reduced by 4.7023 s,and the maximum impulse current is limited to 0.3 A,effectively controlling the impact of large impulse currents and enhancing control efficiency.
文摘The intelligent substation relay protection facility is a fundamental element in construction of modern power system,based on the principles of flexibility,security and accuracy,and it can be divided into process layer and substation layer according to specific equipment.The former is suitable for individual sampling of disposable equipment,can be separated from the base station synchronization sampling,with the help of synchronous digital system and ping-pong algorithm to achieve synchronization of the overall sampling,that is to take the distribution protection components,through the separate transmission medium to realize the information transmission;the latter is for variable power plant components centralized backup protection,taking online real-time tuning technique.
文摘The article discusses the possibility of further modernization of the standard microprocessor relay protection of AC overhead system feeders DPA-27.5-TNF, which is operated on the Trans-Baikal Railway by creating an additional automated system of unified templates necessary for the occurrence of “trainability” elements. The templates will be formed via a separate dedicated channel for transmission, processing and storage of the necessary information, not related to the operation of the terminal, with its subsequent visualization at the workplace of the duty personnel of traction substations, together with information from the “GID” software received via another dedicated wired channel. With the help of such a base of unified preset templates, in the future, it will be possible not only to identify the specific causes of each emergency shutdown but also to reduce their number by dynamically adjusting the existing presets of the standard operation algorithm.
文摘With the development of large-scale complicated modern power systems, the requirement for the associated protection scheme tends to be more stringent and its combination more complex. However, it is very difficult to figure out the factors of failure of such systems. This paper proposes a Petri net model of a transmission line protection relaying system, including three types of relays as well as an automatic reclosing device, and shows how to diagnose serial failure of the system by analyzing invariant sets of the model. Furthermore, it gives four basic types of failure sequences and its execution is much more intuitive and effective than the traditional method.
文摘The research and development of ultra high speed protective relay of transmission line has got great interest and attention of protective relay engineer over the world. Several versions and schemes of ultra high speed relay have been studied and designed in recent twenty years. But only a few of them have got actual apiication in the power system. The relay based on the deviation of power frequency component (DPFC) can get very high reliability with ultra high speed so it has got wide application in Chinese power system. Thousands relay sets have been applied and its operation experience verifies their excellent performance. This paper summarizes the course of the development of the uItra high speed protective relay and compares the merits and defects of the main schemes which have been developed. The principle and successful pratice of the ultra high speed protection based on DPFC reIay are introduced.
文摘This paper presents the existing state anddevelopment planning of East China PowerSystem, which refers to load, power source,power network, system protection, dispatchautomation and system communication.
文摘The article discusses the possibility of a potential reduction in the number of operations of microprocessor relay protection of feeders of the contact network of AC railways TsZA-27.5-FKS (FTS) for unknown reasons. Real statistics on the number of microprocessor relay protection operations at the Buryatskaya traction substation are presented, simulation of the real train situation (in accordance with the regime maps of the throughput capacity of the sections of the Trans-Baikal railway) was carried out in the specialized software complex “KORTES”. Based on the results of the analysis of simulation modeling, the process of forming a unified template of settings using neural network technologies is considered, which characterizes only this specific regular train situation. To protect objects in the event of pre-emergency and emergency modes of operation of the traction power supply system, a variant of changing the standard operation algorithm of the TsZA-27.5-FKS (FTS) terminal by introducing additional blocks for calculating the predictive functions of current and voltage has been proposed.
文摘As the smart grid concepts are emphasized lately, the need to modernize the power engineering education is also well recognized. This paper presents a set of newly developed modeling, simulation and testing tools aimed at better understanding of the design concept and related applications for protective relaying and substation automation solutions for the smart grid. Since the smart grid applications require integration of data from multiple IEDs (intelligent electronic devices), understanding properties of each IED type in detail, as well as their responses to the power system events is needed. In addition, understanding the communication requirements to perform data integration is also important. To illustrate how the mentioned smart grid issues may be taught, the following advanced teaching approaches are presented: (1) Use of modeling and simulation means to better understand interaction between the relays and power system; (2) Use of IED test facilities to better understand performance of physical devices used for protection, monitoring and control; (3) Utilization of communication network modeling tools to simulate the communication network within SAS (substation automation system). Examples showing the use of proposed techniques for teaching the fundamentals and applications are presented. The examples demonstrate the adequacy and efficiency of the proposed techniques.
文摘As the false trips of remote protection relays are among the main reasons behind cascading blackouts, it is critical to design reliable relay protection. Even though common protection schemes on traditional power systems have been investigated for a few decades, cascading failures in recent years indicate more research needed in this area. Consequently, researchers have proposed agent-based methods on the Smart Grid (SG) to address this issue. However, these existing agent-based methods simply use TCP protocol without considering real-time communication requirements (such as bandwidth and delay). To deal with this issue, several methods for efficient network resource management are proposed. Furthermore, these existing methods do not consider the potential issues in practical communication networks, which may result in delay violation and trigger relay false trips. We have discussed simple backup solutions in the previous work. In this paper, in addition to network efficiency, we focus on improving the system reliability by exploring known power system information and minimizing the chances of false trips of important remote relays, e.g., defining power line priorities based on their importance. Moreover, to further improve the. system reliability, we also in- vestigate the peer-to-peer protection approaches to address the single point of failure of centralized control center.
文摘Quasi-PID control method that is able to effectively inhibit the inherent tracking error of PI control method is proposed on the basis of a rounded theoretical analysis of a model of switching power amplifiers (SPAs). To avoid the harmful impacts of the circuit parameter variations and the random disturbances on quasi-PID control method, a single neuron is introduced to endow it with self-adaptability. Quasi-PID control method and the single neuron combine with each other perfectly, and their formation is named as single-neuron adaptive quasi-PID control method. Simulation and experimental results show that single-neuron adaptive quasi-PID control method can accurately track both the predictable and the unpredictable waveforms. Quantitative analysis demonstrates that the accuracy of single-neuron adaptive quasi-PID control method is comparable to that of linear power amplifiers (LPAs) and so can fulfill the requirements of some high-accuracy applications, such as protective relay test. Such accuracy is very difficult to be achieved by many modern control methods for converter controls. Compared with other modern control methods, the programming realization of single-neuron adaptive quasi-PID control method is more suitable for real-time applications and realization on low-end microprocessors for its simple structure and lower computational complexity.
文摘In order to provide a novel and more effective alternative to the commonly used relay protection testing device that outputs only the sinusoidal testing signals, the concept of fault waveform regenerator is proposed in this paper, together with its hardware structure and software flow chart. Fault waveform regenerator mainly depends on its power amplifiers (PAs) to regenerate the fault waveforms recorded by digital fault recorder (DFR). To counteract the PA’s inherent nonlinear distortions, a digital closed-loop modification technique that is different from the predistortion technique is conceived. And the experimental results verify the effectiveness of the fault waveform regenerator based on the digital closed-loop modification technique.
文摘The contradiction of the relay protection with other task has been solved by double CPU’s structure in this comprehensive monitor. Thus the speed of the data processing has raised and the requirement of relay protection and the real bine monitoring has all been satisfied. The input precision of the fault current and the rated current has been assured respectively by applying the relay protection CT and measurement CT. The algorithm of FFT with or without the difference has remarkably raised the precision of the protective measurement and removed the influence of the attenuation DC component in the fault current. Thus the accuracy and reliability of the protective trigger has been raised greatly.
文摘Co-ordination of directional over current relays(DOCR) requires the selection and setting of relays so as to sequentially isolate only that portion of the power system where an abnormality has occurred.The problem of coordinating protective relays in electrical power systems consists of selecting suitable settings such that their fundamental protective function is met,given operational requirements of sensitivity,selectivity,reliability and speed.Directional over current relays are best suited for protection of an interconnected sub-station transmission system.One of the major problems associated with this type of protection is the difficulty in coordinating relays.To insure proper coordination,all the main/back up relay pairs must be determined.This paper presents an effective algorithm to determine the minimum number of break points and main/back up relay pairs using relative sequence matrix(RSM).A novel optimization technique based on evolutionary programming was developed using these main/back up relay pairs for directional over current relay coordination in multi-loop networks.Since the problem has multi-optimum points,conventional mathematics based optimization techniques may sometimes fail.Hence evolutionary programming(EP) was used,as it is a stochastic multi-point search optimization algorithm capable of escaping from the local optimum problem,giving a better chance of reaching a global optimum.The method developed was tested on an existing 6 bus,7 line system and better results were obtained than with conventional methods.