This study investigates the breakdown voltage characteristics in sulfur hexafluoride(SF6)circuit breakers,employing a novel approach that integrates both experimental investigations and finite element simulations.Util...This study investigates the breakdown voltage characteristics in sulfur hexafluoride(SF6)circuit breakers,employing a novel approach that integrates both experimental investigations and finite element simulations.Utilizing a sphere-sphere electrode configuration,we meticulously measured the relationship between breakdown voltage and electrode gap distances ranging from 1 cm to 4.5 cm.Subsequent simulations,conducted using COMSOL Multiphysics,mirrored the experimental setup to validate the model’s accuracy through a comparison of the breakdown voltage-electrode gap distance curves.The simulation results not only aligned closely with the experimental data but also allowed the extraction of detailed electric field strength,electric potential contours,and electric current flow curves at the breakdown voltage for gap distances extending from 1 to 4.5 cm.Extending the analysis,the study explored the electric field and potential distribution at a constant voltage of 72.5 kV for gap distances between 1 to 10 cm,identifying the maximum electric field strength.A comprehensive comparison of five different electrode configurations(sphere-sphere,sphere-rod,sphere-plane,rod-plane,rod-rod)at 72.5 kV and a gap distance of 1.84 cm underscored the significant influence of electrode geometry on the breakdown process.Moreover,the research contrasts the breakdown voltage in SF6 with that in air,emphasizing SF6’s superior insulating properties.This investigation not only elucidates the intricate dynamics of electrical breakdown in SF6 circuit breakers but also contributes valuable insights into the optimal electrode configurations and the potential for alternative insulating gases,steering future advancements in high-voltage circuit breaker technology.展开更多
According to the stream theory, this paper proposes a mathematical model of the dielectric recovery characteristic based on the two-temperature ionization equilibrium equation. Taking the dynamic variation of charged ...According to the stream theory, this paper proposes a mathematical model of the dielectric recovery characteristic based on the two-temperature ionization equilibrium equation. Taking the dynamic variation of charged particle's ionization and attachment into account, this model can be used in collaboration with the Coulomb collision model, which gives the relationship of the heavy particle temperature and electron temperature to calculate the electron density and temperature under different pressure and electric field conditions, so as to deliver the breakdown electric field strength under different pressure conditions. Meanwhile an experiment loop of the circuit breaker has been built to measure the breakdown voltage. It is shown that calculated results are in conformity with experiment results on the whole while results based on the stream criterion are larger than experiment results. This indicates that the mathematical model proposed here is more accurate for calculating the dielectric recovery characteristic, it is derived from the stream model with some improvement and refinement and has great significance for increasing the simulation accuracy of circuit breaker's interruption characteristic.展开更多
The critical electric fields of hot SF6 are calculated including both electron and ion kinetics in wide ranges of temperature and pressure, namely from 300 K up to 4000 K and 2 atmospheres up to 32 atmospheres respect...The critical electric fields of hot SF6 are calculated including both electron and ion kinetics in wide ranges of temperature and pressure, namely from 300 K up to 4000 K and 2 atmospheres up to 32 atmospheres respectively. Based on solving a multi-term electron Boltz- mann equation the calculations use improved electron-gas collision cross sections for twelve SF6 dissociation products with a particular emphasis on the electron-vibrating molecule interactions. The ion kinetics is also considered and its role on the critical field becomes non negligible as the temperature is above 2000 K. These critical fields are then used in hydrodynamics simulations which correctly predict the circuit breaker behaviours observed in the case of breaking tests.展开更多
In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the curren...In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the current at power frequency(50 Hz), power frequency combining the 11 th harmonic and power frequency combining the 24 th harmonic show that the high-order harmonic current would lead to higher decreasing rate of current before current-zero period. In addition, the influence of arc on the amplitude of high-order harmonic current is not negligible. Thus, the coupling of arc with AC filter branch circuit is quite necessary in the numerical modeling of the circuit breaker in the AC filter branch at the high voltage direct current converter station.展开更多
基金Ningbo Science and Technology Plan Project(Grant No.2023Z043)。
文摘This study investigates the breakdown voltage characteristics in sulfur hexafluoride(SF6)circuit breakers,employing a novel approach that integrates both experimental investigations and finite element simulations.Utilizing a sphere-sphere electrode configuration,we meticulously measured the relationship between breakdown voltage and electrode gap distances ranging from 1 cm to 4.5 cm.Subsequent simulations,conducted using COMSOL Multiphysics,mirrored the experimental setup to validate the model’s accuracy through a comparison of the breakdown voltage-electrode gap distance curves.The simulation results not only aligned closely with the experimental data but also allowed the extraction of detailed electric field strength,electric potential contours,and electric current flow curves at the breakdown voltage for gap distances extending from 1 to 4.5 cm.Extending the analysis,the study explored the electric field and potential distribution at a constant voltage of 72.5 kV for gap distances between 1 to 10 cm,identifying the maximum electric field strength.A comprehensive comparison of five different electrode configurations(sphere-sphere,sphere-rod,sphere-plane,rod-plane,rod-rod)at 72.5 kV and a gap distance of 1.84 cm underscored the significant influence of electrode geometry on the breakdown process.Moreover,the research contrasts the breakdown voltage in SF6 with that in air,emphasizing SF6’s superior insulating properties.This investigation not only elucidates the intricate dynamics of electrical breakdown in SF6 circuit breakers but also contributes valuable insights into the optimal electrode configurations and the potential for alternative insulating gases,steering future advancements in high-voltage circuit breaker technology.
基金supported by Science and Technology Project of State Grid Corporation of China(No.GY17201200063)National Natural Science Foundation of China(No.51277123)Basic Research Project of Liaoning Key Laboratory of Education Department(LZ2015055)
文摘According to the stream theory, this paper proposes a mathematical model of the dielectric recovery characteristic based on the two-temperature ionization equilibrium equation. Taking the dynamic variation of charged particle's ionization and attachment into account, this model can be used in collaboration with the Coulomb collision model, which gives the relationship of the heavy particle temperature and electron temperature to calculate the electron density and temperature under different pressure and electric field conditions, so as to deliver the breakdown electric field strength under different pressure conditions. Meanwhile an experiment loop of the circuit breaker has been built to measure the breakdown voltage. It is shown that calculated results are in conformity with experiment results on the whole while results based on the stream criterion are larger than experiment results. This indicates that the mathematical model proposed here is more accurate for calculating the dielectric recovery characteristic, it is derived from the stream model with some improvement and refinement and has great significance for increasing the simulation accuracy of circuit breaker's interruption characteristic.
文摘The critical electric fields of hot SF6 are calculated including both electron and ion kinetics in wide ranges of temperature and pressure, namely from 300 K up to 4000 K and 2 atmospheres up to 32 atmospheres respectively. Based on solving a multi-term electron Boltz- mann equation the calculations use improved electron-gas collision cross sections for twelve SF6 dissociation products with a particular emphasis on the electron-vibrating molecule interactions. The ion kinetics is also considered and its role on the critical field becomes non negligible as the temperature is above 2000 K. These critical fields are then used in hydrodynamics simulations which correctly predict the circuit breaker behaviours observed in the case of breaking tests.
基金supported by the Major Science and Technology Project of China Southern Power Grid Co.,Ltd(ZBKJXM20170065):Research on Harmonic Resonance Mechanism,Suppression Measures and Impact on Main Equipment of AC/DC Hybrid Power Grid。
文摘In this paper, a coupling model of the AC filter branch circuit with the arc plasma in the circuit breaker was built to investigate the arcing process considering the harmonic current. The comparisons among the current at power frequency(50 Hz), power frequency combining the 11 th harmonic and power frequency combining the 24 th harmonic show that the high-order harmonic current would lead to higher decreasing rate of current before current-zero period. In addition, the influence of arc on the amplitude of high-order harmonic current is not negligible. Thus, the coupling of arc with AC filter branch circuit is quite necessary in the numerical modeling of the circuit breaker in the AC filter branch at the high voltage direct current converter station.