The penetration of new energy sources such as wind power is increasing,which consequently increases the occurrence rate of subsynchronous oscillation events.However,existing subsynchronous oscillation source-identific...The penetration of new energy sources such as wind power is increasing,which consequently increases the occurrence rate of subsynchronous oscillation events.However,existing subsynchronous oscillation source-identification methods primarily analyze fixed-mode oscillations and rarely consider time-varying features,such as frequency drift,caused by the random volatility of wind farms when oscillations occur.This paper proposes a subsynchronous oscillation sourcelocalization method that involves an enhanced short-time Fourier transform and a convolutional neural network(CNN).First,an enhanced STFT is performed to secure high-resolution time-frequency distribution(TFD)images from the measured data of the generation unit ports.Next,these TFD images are amalgamated to form a subsynchronous oscillation feature map that serves as input to the CNN to train the localization model.Ultimately,the trained CNN model realizes the online localization of subsynchronous oscillation sources.The effectiveness and accuracy of the proposed method are validated via multimachine system models simulating forced and natural oscillation events using the Power Systems Computer Aided Design platform.Test results show that the proposed method can localize subsynchronous oscillation sources online while considering unpredictable fluctuations in wind farms,thus providing a foundation for oscillation suppression in practical engineering scenarios.展开更多
Semi-floating ring bearing(SFRB) is developed to control the vibration of turbocharger rotor. The outer clearance of SFRB affects the magnitude and frequency of nonlinear whirl motion, which is significant for the d...Semi-floating ring bearing(SFRB) is developed to control the vibration of turbocharger rotor. The outer clearance of SFRB affects the magnitude and frequency of nonlinear whirl motion, which is significant for the design of turbocharger. In order to explore the effects of outer clearance, a transient finite element analysis program for rotor and oil film bearing is built and validated by a published experimental case. The nonlinear dynamic behaviors ofrotor-SFRB system are simulated. According to the simulation results, two representative subsynchronous oscillations excited by the two hearings respectively are discovered. As the outer clearance of SFRB increases from 24 ~tm to 60 pro, the low-frequency subsynchronous oscillation experiences three steps, including a strong start, a gradual recession and a combination with the other one. At the same time, the high-frequency subsynchronous oscillation starts to appear gradually, then strengthens, and finally combines. If gravity and unbalance are neglected, the combination will start starts from high rotor speed and extents to low rotor speed, just like a "zipper". It is found from the quantitative analysis that when the outer clearance increases, the vibration amplitude experiences large value firstly, then reduction, and suddenly increasing after combination. A useful design principle of SFRB outer clearance for minimum vibration amplitude is proposed: the outer clearance value should be chosen to keep the frequency of two subsynchronous oscillations clearly separated and their amplitudes close.展开更多
Owing to the large-scale grid connection of new energy sources, several installed power electronic devices introduce sub-/supersynchronous inter-harmonics into power signals, resulting in the frequent occurrence of su...Owing to the large-scale grid connection of new energy sources, several installed power electronic devices introduce sub-/supersynchronous inter-harmonics into power signals, resulting in the frequent occurrence of subsynchronous oscillations(SSOs). The SSOs may cause significant harm to generator sets and power systems;thus, online monitoring and accurate alarms for power systems are crucial for their safe and stable operation. Phasor measurement units(PMUs) can realize the dynamic real-time monitoring of power systems. Based on PMU phasor measurements, this study proposes a method for SSO online monitoring and alarm implementation for the main station of a PMU. First, fast Fourier transform frequency spectrum analysis is performed on PMU current phasor amplitude data to obtain subsynchronous frequency components. Second, the support vector machine learning algorithm is trained to obtain the amplitude threshold and subsequently filter out safe components and retain harmful ones. Finally, the adaptive duration threshold is determined according to frequency susceptibility, amplitude attenuation, and energy accumulation to decide whether to transmit an alarm signal. Experiments based on field data verify the effectiveness of the proposed method.展开更多
The subsynchronous oscillations(SSOs)related to renewable generation seriously affect the stability and safety of the power systems.To realize the dynamic monitoring of SSOs by utilizing the high computational efficie...The subsynchronous oscillations(SSOs)related to renewable generation seriously affect the stability and safety of the power systems.To realize the dynamic monitoring of SSOs by utilizing the high computational efficiency and noise-resilient features of the matrix pencil method(MPM),this paper propos es an improved MPM-based parameter identification with syn chrophasors.The MPM is enhanced by the angular frequency fitting equations based on the characteristic polynomial coeffi cients of the matrix pencil to ensure the accuracy of the identi fied parameters,since the existing eigenvalue solution of the MPM ignores the angular frequency conjugation constraints of the two fundamental modes and two oscillation modes.Then,the identification and recovery of bad data are proposed by uti lizing the difference in temporal continuity of the synchropha sors before and after noise reduction.The proposed parameter identification is verified with synthetic,simulated,and actual measured phase measurement unit(PMU)data.Compared with the existing MPM,the improved MPM achieves better accuracy for parameter identification of each component in SSOs,better real-time performance,and significantly reduces the effect of bad data.展开更多
Subsynchronous oscillation (SSO) with low amplitude that exceeds cumulative fatigue threshold of the generator shaft frequently could significantly reduce the shaft's service life, which is a new SSO problem that ...Subsynchronous oscillation (SSO) with low amplitude that exceeds cumulative fatigue threshold of the generator shaft frequently could significantly reduce the shaft's service life, which is a new SSO problem that emerges in recent years. According to the real recording oscillograph, the basic reason for frequently over-threshold SSO with low amplitude at multi-power plants was analyzed based on Hulunbuir League system. The sensitivities of the electrical damping to the main electrical parameters in the contributing loop of subsynchronous torsional interaction were calculated. Based on the sensitivities, a simulation method was presented, which was used to excite the same oscillation as the actual case by exerting disturbance on the firing angle. The limitation of wide-band and narrow-band supplementary subsynchronous damping controller (SSDC) for mitigating this kind of SSO was analyzed based on the electromagnetic transient simulation model of Hulunbuir League system. The difference of supplementary excitation damping controller (SEDC) and parallel-form FACTS connected to the generator terminal was compared from the aspects of response time and the ability of damping torque supplying. The analysis indicates that their response time is similar but FACTS has stronger ability of damping torque supplying than SEDC. Time-domain simulation method was used to compare the mitigation effects of SEDC, static var compensator (SVC) and static synchronous compensator (STATCOM). Considering the mitigation effect, the floor space limit of the power plant and so on, STATCOM was considered as the best mitigation measure. A control strategy of cascaded STATCOM for engineering application was presented and the capacity for SSO mitigation as well as output characteristics was analyzed. The analysis indicates that STATCOM using the proposed control strategy has better mitigation effect and output characteristics with smaller capacity.展开更多
At present,the direct drive permanent magnet synchronous generator(DD-PMSG)grid connected system based on virtual synchronous generator(VSG)control will experience power oscillation at sub synchronous frequencies.The ...At present,the direct drive permanent magnet synchronous generator(DD-PMSG)grid connected system based on virtual synchronous generator(VSG)control will experience power oscillation at sub synchronous frequencies.The mechanism and characteristics of this new type of sub-synchronous interaction(SSI)are not yet clear,and the system cannot recover to steady state solely based on the characteristics of VSG itself.Especially when connected to a weak current network,oscillations are more pronounced,affecting the stability of the system.In severe cases,the systemmay trigger shutdown protection and be disconnected from the network.Existing research has only analyzed the oscillation mechanism under this phenomenon and has not proposed corresponding control strategies.This article proposes aVSM control strategy based on the VSG control algorithm,which balances the dq axis component of voltage and current,and improves the voltage and current loop of VSG control to reduce the impact of sub-synchronous oscillation(SSO)on the power grid.In MATLAB/Simulink,a simulation model of the proposed control strategy was built to verify its correctness and effectiveness.展开更多
Phasor measurement units(PMU) are playing an increasingly important role in power system dynamic security monitoring and control. However, the wide-area deployments of the renewable energy sources and the high voltage...Phasor measurement units(PMU) are playing an increasingly important role in power system dynamic security monitoring and control. However, the wide-area deployments of the renewable energy sources and the high voltage direct current(HVDC) transmission bring a large number of inter-harmonics to the power grid, which may result in further power system security problems. The impacts of inter-harmonics on synchrophasor measurements are revealed. This paper derives the phasor expressions of the signal, which contains the fundamental component and the inter-harmonics. It is found that the inter-harmonics will lead to the subsynchronous oscillation of the phasor measurements. The frequency transmutation principle between the harmonic and the phasor oscillation is revealed. Then, the field PMU data recorded during a subsynchronous oscillation, which occurred in an area of China with a high concentration of wind farms and HVDC transmission lines, are studied. A geographical wiring diagram with the subsynchronous oscillation distribution depicts the severe consequences of the inter-harmonics. In addition, the correctness of the theoretical derivation and the possibility of the inter-harmonics monitoring are verified.展开更多
With the increasing capacity of wind farm, HVDC technology has become a promising transmission scheme for long distance transportation of large-scale wind power. However oscillation caused by this system will have a g...With the increasing capacity of wind farm, HVDC technology has become a promising transmission scheme for long distance transportation of large-scale wind power. However oscillation caused by this system will have a great influence on the security and stability of power system operation. In this paper, the oscillation of a doubly-fed induction generator(DFIG)-based wind farm interfaced with line commutated converter(LCC) based HVDC is discussed. Low-frequency oscillation and subsynchronous oscillation(SSO) are studied since these two oscillations are the particularly concerned oscillations in the stability study of power system in recent years. The model of a DFIG-based wind farm interconnected with LCC-HVDC is developed. The impact of drive train model's structure and parameters on the oscillation characteristics is analyzed. Eigenvalue and participation factor analysis are used to identify the three main modes, which include controller mode, electromechanical mode, and shaft mode. The effects of DFIG controller's parameters, wind speed and operating conditions of HVDC on those modes are studied. Electromagnetic transient simulations are performed to verify the results of the eigenvalue analysis.展开更多
Currently, the power electronics-based devices, includinglarge-scale non-synchronized generators and reactivepower compensators, are widely used in power grids. This helpsintroduce the coupling interactions between th...Currently, the power electronics-based devices, includinglarge-scale non-synchronized generators and reactivepower compensators, are widely used in power grids. This helpsintroduce the coupling interactions between the devices andthe power grid, resulting in a new sub-synchronous oscillationphenomenon. It is a critical element for the stability operation ofthe power grid and its devices. In this paper, the sub-synchronousoscillation phenomenon of the power grid connected with largescalewind power generation is analyzed in detail. Then, inorder to damp the sub-synchronous oscillation, a coordinateddamping optimization control strategy for wind power generatorsand their reactive power compensators is proposed. The proposedcoordinated control strategy tracks the sub-synchronousoscillation current signal to correct the corresponding controlsignal, which increases the damping of power electronics. Theresponse characteristics of the proposed control strategy areanalyzed, and a self-optimization parameter tuning method basedon sensitivity analysis is proposed. The simulation results validatethe effectiveness and the availability of the proposed controlstrategy.展开更多
With the rapid development of inverter-based generators(IGs),power grid is faced with critical frequency stability challenges because the existing IGs have no inertia.To equip IGs with inertial response,researchers ha...With the rapid development of inverter-based generators(IGs),power grid is faced with critical frequency stability challenges because the existing IGs have no inertia.To equip IGs with inertial response,researchers have proposed several virtual inertia control methods,which can be classified into two categories:virtual synchronous generator(VSG)control and droop control based on rate of change of frequency(ROCOFdroop control).In this paper,the comparison between both virtual inertia control methods is conducted from three perspectives:mathematical model,output characteristic and small-signal stability.State-space models are firstly built to analyze the control mechanism of VSG control and ROCOF-droop control methods.Simulation and eigenvalue analysis are conducted to study the transient responses and oscillation characteristics of both methods,which is helpful to understand the advantages and limitations of existing virtual inertia control methods.Finally,the obtained theoretical results are validated through realtime laboratory(RT-LAB)hardware-in-loop simulation platform.展开更多
The creation of a suitable wide area monitoring system(WAMS) is widely recognized as an essential aspect of delivering a power system that will be secure,efficient and sustainable for the foreseeable future. In Great ...The creation of a suitable wide area monitoring system(WAMS) is widely recognized as an essential aspect of delivering a power system that will be secure,efficient and sustainable for the foreseeable future. In Great Britain(GB), the deployment of the first WAMS to monitor the entire power system in real time was the responsibility of the visualization of real time system dynamics using enhanced monitoring(VISOR) project. The core scope of the VISOR project is to deploy this WAMS and demonstrate how WAMS applications can in the near term provide system operators and planners with clear, actionable information. This paper presents the wider scope of the VISOR project and the GB wide WAMS that has been deployed. Furthermore, the paper describes some of the WAMS applications that have been deployed and provides examples of the measurement device performance issues that have been encountered during the project.展开更多
In a grid-connected wind farm based on permanent magnet synchronous generators(PMSGs),the wind speed and the number of operating PMSGs are the two most important influencing factors along with the stochastic nature of...In a grid-connected wind farm based on permanent magnet synchronous generators(PMSGs),the wind speed and the number of operating PMSGs are the two most important influencing factors along with the stochastic nature of sub-synchronous oscillation(SSO)from the point view of the farm.This paper proposes a method of unstable SSO risk evaluation for grid-connected PMSG-based wind farms based on the sequential Monte Carlo simulation(SMCS).The determination of critical wind speed(CWS)of SSO and the sequential simulation strategy of wind speed states and PMSG states in a wind farm at the same wind speed(S-WF),as well as in a wind farm at different wind speeds(D-WF),are studied.Five indices evaluating the expectation,duration,frequency and energy loss of SsO risk are proposed.Moreover,a strategy to reduce SsO risk by adjusting the cut-in wind speed is discussed.The effectiveness of the discussed issues in this paper are proved by the case studies of a 750-PMSG wind farm based on the actual wind speed data collected.展开更多
基金supported by the Science and Technology Project of State Grid Corporation of China(5100202199536A-0-5-ZN)。
文摘The penetration of new energy sources such as wind power is increasing,which consequently increases the occurrence rate of subsynchronous oscillation events.However,existing subsynchronous oscillation source-identification methods primarily analyze fixed-mode oscillations and rarely consider time-varying features,such as frequency drift,caused by the random volatility of wind farms when oscillations occur.This paper proposes a subsynchronous oscillation sourcelocalization method that involves an enhanced short-time Fourier transform and a convolutional neural network(CNN).First,an enhanced STFT is performed to secure high-resolution time-frequency distribution(TFD)images from the measured data of the generation unit ports.Next,these TFD images are amalgamated to form a subsynchronous oscillation feature map that serves as input to the CNN to train the localization model.Ultimately,the trained CNN model realizes the online localization of subsynchronous oscillation sources.The effectiveness and accuracy of the proposed method are validated via multimachine system models simulating forced and natural oscillation events using the Power Systems Computer Aided Design platform.Test results show that the proposed method can localize subsynchronous oscillation sources online while considering unpredictable fluctuations in wind farms,thus providing a foundation for oscillation suppression in practical engineering scenarios.
基金Supported by National Natural Science Foundation of China(Grant No51506108)
文摘Semi-floating ring bearing(SFRB) is developed to control the vibration of turbocharger rotor. The outer clearance of SFRB affects the magnitude and frequency of nonlinear whirl motion, which is significant for the design of turbocharger. In order to explore the effects of outer clearance, a transient finite element analysis program for rotor and oil film bearing is built and validated by a published experimental case. The nonlinear dynamic behaviors ofrotor-SFRB system are simulated. According to the simulation results, two representative subsynchronous oscillations excited by the two hearings respectively are discovered. As the outer clearance of SFRB increases from 24 ~tm to 60 pro, the low-frequency subsynchronous oscillation experiences three steps, including a strong start, a gradual recession and a combination with the other one. At the same time, the high-frequency subsynchronous oscillation starts to appear gradually, then strengthens, and finally combines. If gravity and unbalance are neglected, the combination will start starts from high rotor speed and extents to low rotor speed, just like a "zipper". It is found from the quantitative analysis that when the outer clearance increases, the vibration amplitude experiences large value firstly, then reduction, and suddenly increasing after combination. A useful design principle of SFRB outer clearance for minimum vibration amplitude is proposed: the outer clearance value should be chosen to keep the frequency of two subsynchronous oscillations clearly separated and their amplitudes close.
基金supported by the National Key R&D Pro gram (2017YFB0902901)National Nature Science Founda tion of China (51725702, 51627811, 51707064)。
文摘Owing to the large-scale grid connection of new energy sources, several installed power electronic devices introduce sub-/supersynchronous inter-harmonics into power signals, resulting in the frequent occurrence of subsynchronous oscillations(SSOs). The SSOs may cause significant harm to generator sets and power systems;thus, online monitoring and accurate alarms for power systems are crucial for their safe and stable operation. Phasor measurement units(PMUs) can realize the dynamic real-time monitoring of power systems. Based on PMU phasor measurements, this study proposes a method for SSO online monitoring and alarm implementation for the main station of a PMU. First, fast Fourier transform frequency spectrum analysis is performed on PMU current phasor amplitude data to obtain subsynchronous frequency components. Second, the support vector machine learning algorithm is trained to obtain the amplitude threshold and subsequently filter out safe components and retain harmful ones. Finally, the adaptive duration threshold is determined according to frequency susceptibility, amplitude attenuation, and energy accumulation to decide whether to transmit an alarm signal. Experiments based on field data verify the effectiveness of the proposed method.
基金supported by National Natural Science Foundation of China(No.52077004).
文摘The subsynchronous oscillations(SSOs)related to renewable generation seriously affect the stability and safety of the power systems.To realize the dynamic monitoring of SSOs by utilizing the high computational efficiency and noise-resilient features of the matrix pencil method(MPM),this paper propos es an improved MPM-based parameter identification with syn chrophasors.The MPM is enhanced by the angular frequency fitting equations based on the characteristic polynomial coeffi cients of the matrix pencil to ensure the accuracy of the identi fied parameters,since the existing eigenvalue solution of the MPM ignores the angular frequency conjugation constraints of the two fundamental modes and two oscillation modes.Then,the identification and recovery of bad data are proposed by uti lizing the difference in temporal continuity of the synchropha sors before and after noise reduction.The proposed parameter identification is verified with synthetic,simulated,and actual measured phase measurement unit(PMU)data.Compared with the existing MPM,the improved MPM achieves better accuracy for parameter identification of each component in SSOs,better real-time performance,and significantly reduces the effect of bad data.
基金supported by the Key Project of the National 12th Five-Year Research Programme of China (Grant No. 2011BAA01B02)the Fundamental Research Funds for the Central Universities of China (Grant No.12QN37)
文摘Subsynchronous oscillation (SSO) with low amplitude that exceeds cumulative fatigue threshold of the generator shaft frequently could significantly reduce the shaft's service life, which is a new SSO problem that emerges in recent years. According to the real recording oscillograph, the basic reason for frequently over-threshold SSO with low amplitude at multi-power plants was analyzed based on Hulunbuir League system. The sensitivities of the electrical damping to the main electrical parameters in the contributing loop of subsynchronous torsional interaction were calculated. Based on the sensitivities, a simulation method was presented, which was used to excite the same oscillation as the actual case by exerting disturbance on the firing angle. The limitation of wide-band and narrow-band supplementary subsynchronous damping controller (SSDC) for mitigating this kind of SSO was analyzed based on the electromagnetic transient simulation model of Hulunbuir League system. The difference of supplementary excitation damping controller (SEDC) and parallel-form FACTS connected to the generator terminal was compared from the aspects of response time and the ability of damping torque supplying. The analysis indicates that their response time is similar but FACTS has stronger ability of damping torque supplying than SEDC. Time-domain simulation method was used to compare the mitigation effects of SEDC, static var compensator (SVC) and static synchronous compensator (STATCOM). Considering the mitigation effect, the floor space limit of the power plant and so on, STATCOM was considered as the best mitigation measure. A control strategy of cascaded STATCOM for engineering application was presented and the capacity for SSO mitigation as well as output characteristics was analyzed. The analysis indicates that STATCOM using the proposed control strategy has better mitigation effect and output characteristics with smaller capacity.
文摘At present,the direct drive permanent magnet synchronous generator(DD-PMSG)grid connected system based on virtual synchronous generator(VSG)control will experience power oscillation at sub synchronous frequencies.The mechanism and characteristics of this new type of sub-synchronous interaction(SSI)are not yet clear,and the system cannot recover to steady state solely based on the characteristics of VSG itself.Especially when connected to a weak current network,oscillations are more pronounced,affecting the stability of the system.In severe cases,the systemmay trigger shutdown protection and be disconnected from the network.Existing research has only analyzed the oscillation mechanism under this phenomenon and has not proposed corresponding control strategies.This article proposes aVSM control strategy based on the VSG control algorithm,which balances the dq axis component of voltage and current,and improves the voltage and current loop of VSG control to reduce the impact of sub-synchronous oscillation(SSO)on the power grid.In MATLAB/Simulink,a simulation model of the proposed control strategy was built to verify its correctness and effectiveness.
文摘Phasor measurement units(PMU) are playing an increasingly important role in power system dynamic security monitoring and control. However, the wide-area deployments of the renewable energy sources and the high voltage direct current(HVDC) transmission bring a large number of inter-harmonics to the power grid, which may result in further power system security problems. The impacts of inter-harmonics on synchrophasor measurements are revealed. This paper derives the phasor expressions of the signal, which contains the fundamental component and the inter-harmonics. It is found that the inter-harmonics will lead to the subsynchronous oscillation of the phasor measurements. The frequency transmutation principle between the harmonic and the phasor oscillation is revealed. Then, the field PMU data recorded during a subsynchronous oscillation, which occurred in an area of China with a high concentration of wind farms and HVDC transmission lines, are studied. A geographical wiring diagram with the subsynchronous oscillation distribution depicts the severe consequences of the inter-harmonics. In addition, the correctness of the theoretical derivation and the possibility of the inter-harmonics monitoring are verified.
基金supported by the National Hi-Tech Research and Development Program of China("863"Project)(Grant No.2011AA05A301)"111"Project of China(Grant No.B08013)
文摘With the increasing capacity of wind farm, HVDC technology has become a promising transmission scheme for long distance transportation of large-scale wind power. However oscillation caused by this system will have a great influence on the security and stability of power system operation. In this paper, the oscillation of a doubly-fed induction generator(DFIG)-based wind farm interfaced with line commutated converter(LCC) based HVDC is discussed. Low-frequency oscillation and subsynchronous oscillation(SSO) are studied since these two oscillations are the particularly concerned oscillations in the stability study of power system in recent years. The model of a DFIG-based wind farm interconnected with LCC-HVDC is developed. The impact of drive train model's structure and parameters on the oscillation characteristics is analyzed. Eigenvalue and participation factor analysis are used to identify the three main modes, which include controller mode, electromechanical mode, and shaft mode. The effects of DFIG controller's parameters, wind speed and operating conditions of HVDC on those modes are studied. Electromagnetic transient simulations are performed to verify the results of the eigenvalue analysis.
基金the NationalNatural Science Foundation of China under Grant No.51577174.
文摘Currently, the power electronics-based devices, includinglarge-scale non-synchronized generators and reactivepower compensators, are widely used in power grids. This helpsintroduce the coupling interactions between the devices andthe power grid, resulting in a new sub-synchronous oscillationphenomenon. It is a critical element for the stability operation ofthe power grid and its devices. In this paper, the sub-synchronousoscillation phenomenon of the power grid connected with largescalewind power generation is analyzed in detail. Then, inorder to damp the sub-synchronous oscillation, a coordinateddamping optimization control strategy for wind power generatorsand their reactive power compensators is proposed. The proposedcoordinated control strategy tracks the sub-synchronousoscillation current signal to correct the corresponding controlsignal, which increases the damping of power electronics. Theresponse characteristics of the proposed control strategy areanalyzed, and a self-optimization parameter tuning method basedon sensitivity analysis is proposed. The simulation results validatethe effectiveness and the availability of the proposed controlstrategy.
基金supported by the technology project of State Grid Corporation of China and the technology project of State Grid Jibei Electric Power Corporation
文摘With the rapid development of inverter-based generators(IGs),power grid is faced with critical frequency stability challenges because the existing IGs have no inertia.To equip IGs with inertial response,researchers have proposed several virtual inertia control methods,which can be classified into two categories:virtual synchronous generator(VSG)control and droop control based on rate of change of frequency(ROCOFdroop control).In this paper,the comparison between both virtual inertia control methods is conducted from three perspectives:mathematical model,output characteristic and small-signal stability.State-space models are firstly built to analyze the control mechanism of VSG control and ROCOF-droop control methods.Simulation and eigenvalue analysis are conducted to study the transient responses and oscillation characteristics of both methods,which is helpful to understand the advantages and limitations of existing virtual inertia control methods.Finally,the obtained theoretical results are validated through realtime laboratory(RT-LAB)hardware-in-loop simulation platform.
基金supported by the GB Network Innovation Competition(NIC)
文摘The creation of a suitable wide area monitoring system(WAMS) is widely recognized as an essential aspect of delivering a power system that will be secure,efficient and sustainable for the foreseeable future. In Great Britain(GB), the deployment of the first WAMS to monitor the entire power system in real time was the responsibility of the visualization of real time system dynamics using enhanced monitoring(VISOR) project. The core scope of the VISOR project is to deploy this WAMS and demonstrate how WAMS applications can in the near term provide system operators and planners with clear, actionable information. This paper presents the wider scope of the VISOR project and the GB wide WAMS that has been deployed. Furthermore, the paper describes some of the WAMS applications that have been deployed and provides examples of the measurement device performance issues that have been encountered during the project.
基金supported by the National Natural Science Foundation of China under Grant(51777066).
文摘In a grid-connected wind farm based on permanent magnet synchronous generators(PMSGs),the wind speed and the number of operating PMSGs are the two most important influencing factors along with the stochastic nature of sub-synchronous oscillation(SSO)from the point view of the farm.This paper proposes a method of unstable SSO risk evaluation for grid-connected PMSG-based wind farms based on the sequential Monte Carlo simulation(SMCS).The determination of critical wind speed(CWS)of SSO and the sequential simulation strategy of wind speed states and PMSG states in a wind farm at the same wind speed(S-WF),as well as in a wind farm at different wind speeds(D-WF),are studied.Five indices evaluating the expectation,duration,frequency and energy loss of SsO risk are proposed.Moreover,a strategy to reduce SsO risk by adjusting the cut-in wind speed is discussed.The effectiveness of the discussed issues in this paper are proved by the case studies of a 750-PMSG wind farm based on the actual wind speed data collected.