Magnetically coupled resonant technology is a novel method for solving the breakpoint locating of power grounding grid.But the method can only detect breakpoints of a single mesh grounding grid at present.In this pape...Magnetically coupled resonant technology is a novel method for solving the breakpoint locating of power grounding grid.But the method can only detect breakpoints of a single mesh grounding grid at present.In this paper,a magnetically coupled resonant detection method for four-hole grounding grid breakpoint is proposed.Firstly,the equivalent circuit model of the four mesh grounding grid with two types of breakpoints,namely edge branch and intermediate branch,is established.The input impedance and phase angle of the system are obtained by analyzing the equivalent capacitance and equivalent resistance in the model.Secondly,the magnetically coupled resonant physical process of grounding grid faults is solved via HFSS software.The magnetic field intensity and phase frequency characteristic curves of four mesh holes with different branches and positions of breakpoints and different corrosion degrees are studied,and an experimental system is built to verify the feasibility.The results show that under the condition of grounding grid buried depth of 0.5 m and input frequency of 1~15MHz,and there is an inverse relationship between equivalent capacitance and distortion frequency,the phase angle is positively correlated with the degree of corrosion of grounding grid,and the error of signal distortion frequency can be positioned at 5%.This paper provides some ideas for the application of magnetic coupling grounding grid detection technology.展开更多
In this study, we observe a strong inverse magnetoelectric coupling in Fe52.5Co22.5B25.0/PZN-PT multiferroic heterostructure, which produces large electric field(E-field) tunability of microwave magnetic properties....In this study, we observe a strong inverse magnetoelectric coupling in Fe52.5Co22.5B25.0/PZN-PT multiferroic heterostructure, which produces large electric field(E-field) tunability of microwave magnetic properties. With the increase of the E-field from 0 to 8 kV/cm, the magnetic anisotropy field Heffis dramatically enhanced from 169 to 600 Oe, which further leads to a significant enhancement of ferromagnetic resonance frequency from 4.57 to 8.73 GHz under zero bias magnetic field, and a simultaneous decrease of the damping constant α from 0.021 to 0.0186. These features demonstrate that this multiferroic composite is a promising candidate for fabricating E-field tunable microwave components.展开更多
基金supported by the Science and Technology Research Innovation Team Project LT2019007 of the Department of Education of Liaoning Provincethe Discipline Innovation Team Project LNTU20TD-02,29 of Liaoning Technical University。
文摘Magnetically coupled resonant technology is a novel method for solving the breakpoint locating of power grounding grid.But the method can only detect breakpoints of a single mesh grounding grid at present.In this paper,a magnetically coupled resonant detection method for four-hole grounding grid breakpoint is proposed.Firstly,the equivalent circuit model of the four mesh grounding grid with two types of breakpoints,namely edge branch and intermediate branch,is established.The input impedance and phase angle of the system are obtained by analyzing the equivalent capacitance and equivalent resistance in the model.Secondly,the magnetically coupled resonant physical process of grounding grid faults is solved via HFSS software.The magnetic field intensity and phase frequency characteristic curves of four mesh holes with different branches and positions of breakpoints and different corrosion degrees are studied,and an experimental system is built to verify the feasibility.The results show that under the condition of grounding grid buried depth of 0.5 m and input frequency of 1~15MHz,and there is an inverse relationship between equivalent capacitance and distortion frequency,the phase angle is positively correlated with the degree of corrosion of grounding grid,and the error of signal distortion frequency can be positioned at 5%.This paper provides some ideas for the application of magnetic coupling grounding grid detection technology.
基金Project supported by the National Natural Science Foundation of China(Grant No.11674187)
文摘In this study, we observe a strong inverse magnetoelectric coupling in Fe52.5Co22.5B25.0/PZN-PT multiferroic heterostructure, which produces large electric field(E-field) tunability of microwave magnetic properties. With the increase of the E-field from 0 to 8 kV/cm, the magnetic anisotropy field Heffis dramatically enhanced from 169 to 600 Oe, which further leads to a significant enhancement of ferromagnetic resonance frequency from 4.57 to 8.73 GHz under zero bias magnetic field, and a simultaneous decrease of the damping constant α from 0.021 to 0.0186. These features demonstrate that this multiferroic composite is a promising candidate for fabricating E-field tunable microwave components.