Optimization Analysis of High Temperature Heat Pump Coupling to Desiccant Wheel Air Conditioning System 被引量:1
1
作者 盛颖 张于峰 +2 位作者 房磊 聂金哲 马丽筠 《Transactions of Tianjin University》 EI CAS 2014年第3期182-188,共7页
The high temperature heat pump and desiccant wheel(HTHP&DW) system can make full use of heat released from the condenser of heat pump for DW regeneration without additional heat. In this study, DW operation in the... The high temperature heat pump and desiccant wheel(HTHP&DW) system can make full use of heat released from the condenser of heat pump for DW regeneration without additional heat. In this study, DW operation in the HTHP&DW system was investigated experimentally, and the optimization analysis of HTHP&DW system was carried out. The performance of DW had influence on the dehumidification(evaluated by dehumidification and regeneration effectiveness) and cooling load(evaluated by thermal and adiabatic effectiveness). The results show that the enthalpy increase occurred in all the experiments. Compared to the isosteric heat, heat accumulation in the desiccant and matrix material and heat leakage from regeneration side to process side have greater influence on the adiabatic effectiveness. Higher regeneration temperature leads to lower adiabatic effectiveness that increases more cooling load of the system. When the regeneration temperature is 63℃, the maximal dehumidification effectiveness is 35.4% and the satisfied adiabatic effectiveness is 88%, which contributes to the optimal balance between dehumidification and cooling. 展开更多
关键词 desiccant wheel DEHUMIDIFICATION adiabatic effectiveness performance optimization