Arcing Model of a Disconnector and its Effect on VFTO 被引量:6
1
作者 林莘 王娜 徐建源 《Plasma Science and Technology》 SCIE EI CAS CSCD 2013年第7期644-647,共4页
In the computational process of very fast transient over-voltage (VFTO), it is essen-tial to find an accurate model for a gas insulated substation. The arcing model of the disconnector is particularly important. The... In the computational process of very fast transient over-voltage (VFTO), it is essen-tial to find an accurate model for a gas insulated substation. The arcing model of the disconnector is particularly important. The general arcing model is not able to give a good description of the arc development process. In this paper, based on the physical process of arcing and existing arc models (the exponential time-varying resistance model and the segmental arcing models), a dy- namic arcing model is proposed, which is divided into two stages before and after the zero crossing. The dynamic arcing model combines hyperbola time-varying resistance and the Mayr model to describe the dynamic process of arcing. The present paper creates an arc model blockset upon the Matlab/Simulink software platform. Moreover for a specific 1100 kV station, VFTO is simulated in detail based on different arcing models. It is demonstrated that the dynamic arcing model can describe the physical arc process precisely and is useful for improving the accuracy of VFTO simulations. 展开更多
关键词 disconnector switching UHV dynamic arcing model gas insulated substa-tion VFTO