To meet the requirement of fire endurance for concrete structures strengthened with CFRP sheets, this study develops an inorganic adhesive whose strength at 600 ℃ is not lower than that at normal room temperature. Th...To meet the requirement of fire endurance for concrete structures strengthened with CFRP sheets, this study develops an inorganic adhesive whose strength at 600 ℃ is not lower than that at normal room temperature. The inorganic adhesive is then used to bond CFRP sheets on reinforced concrete beams in order to strengthen them. The fire protection of the CFRP sheets is done using the thick-type fireproofing coatings for tunnel ( TFCT) and steel structure ( TFCSS) respectively. Four specimens are tested in the furnace together. Specimens are exposed to fire for 1. 5 h in according to the ISO834 standard fire curve,and then naturally cooled for 1 h. In the tests,the largest displacements at the mid-span positions of specimens are only from 1 /1400 to 1 /318 of actual span corresponding to the highest temperatures from 300 ℃ to 470 ℃. After the specimens are naturally cooled to the normal temperature and the fireproofing coatings are then removed,it can be seen that the CFRP sheets keep in a good state,which indicates that CFRP sheets can be tightly bonded on the concrete and work well together with the concrete beams during and after fire. Besides,the tests also verify that the fire performance of TFCT is superior to TFCSS for the strengthened beams.展开更多
基金Sponsored by Changjiang Scholars Program of China( Grant No 2009-37)the National Natural Science Foundation of China( Grant No 50678050)Innovative Science Foundation of HIT ( Grant No HIT2005C-3)
文摘To meet the requirement of fire endurance for concrete structures strengthened with CFRP sheets, this study develops an inorganic adhesive whose strength at 600 ℃ is not lower than that at normal room temperature. The inorganic adhesive is then used to bond CFRP sheets on reinforced concrete beams in order to strengthen them. The fire protection of the CFRP sheets is done using the thick-type fireproofing coatings for tunnel ( TFCT) and steel structure ( TFCSS) respectively. Four specimens are tested in the furnace together. Specimens are exposed to fire for 1. 5 h in according to the ISO834 standard fire curve,and then naturally cooled for 1 h. In the tests,the largest displacements at the mid-span positions of specimens are only from 1 /1400 to 1 /318 of actual span corresponding to the highest temperatures from 300 ℃ to 470 ℃. After the specimens are naturally cooled to the normal temperature and the fireproofing coatings are then removed,it can be seen that the CFRP sheets keep in a good state,which indicates that CFRP sheets can be tightly bonded on the concrete and work well together with the concrete beams during and after fire. Besides,the tests also verify that the fire performance of TFCT is superior to TFCSS for the strengthened beams.