Based on the comparison of existing power flow controllers(PFC)in meshed HVDC grids,the full-bridge modular multilevel converter based PFC(MMPFC)is proposed.At first,the general branch current calculation method of me...Based on the comparison of existing power flow controllers(PFC)in meshed HVDC grids,the full-bridge modular multilevel converter based PFC(MMPFC)is proposed.At first,the general branch current calculation method of meshed HVDC grids with the PFC is presented,and then,the issue of over-voltage on the thyristor based PFC is described and analyzed.Through the analysis of different operating modes of the full-bridge sub-module,the mechanism of over-voltage ride through of the MMPFC is indicated.The control strategy of the MMPFC,which is used to control branch current and keep capacitor voltage balancing,is elaborated.Finally,the performance on current regulation,bidirectional operation and over-voltage ride through is simulated and verified in a built model with PSCAD/EMTDC.展开更多
To reduce the probability of commutation failure(CF)of a line commutated converter based high-voltage direct current(LCC-HVDC)transmission,a DC chopper topology composed of power consumption sub-modules based on thyri...To reduce the probability of commutation failure(CF)of a line commutated converter based high-voltage direct current(LCC-HVDC)transmission,a DC chopper topology composed of power consumption sub-modules based on thyristor full-bridge module(TFB-PCSM)is proposed.Firstly,the mechanism of the proposed topology to mitigate CF is analyzed,and the working modes of TFB-PCSM in different operation states are introduced.Secondly,the coordinated control strategy between the proposed DC chopper and LCC-HVDC is designed,and the voltage-current stresses of the TFB-PCSMs are investigated.Finally,the ability to mitigate the CF issues and the fault recovery performance of LCC-HVDC system are studied in PSCAD/EMTDC.The results show that the probability of CF of LCC-HVDC is significantly reduced,and the performances of fault recovery are effectively improved by the proposed DC chopper.展开更多
基金supported by the National High Technology Research and Development Program of China("863"Program)(Grant No.2012AA050205)
文摘Based on the comparison of existing power flow controllers(PFC)in meshed HVDC grids,the full-bridge modular multilevel converter based PFC(MMPFC)is proposed.At first,the general branch current calculation method of meshed HVDC grids with the PFC is presented,and then,the issue of over-voltage on the thyristor based PFC is described and analyzed.Through the analysis of different operating modes of the full-bridge sub-module,the mechanism of over-voltage ride through of the MMPFC is indicated.The control strategy of the MMPFC,which is used to control branch current and keep capacitor voltage balancing,is elaborated.Finally,the performance on current regulation,bidirectional operation and over-voltage ride through is simulated and verified in a built model with PSCAD/EMTDC.
基金supported by National Natural Science Foundation of China(No.51877077)。
文摘To reduce the probability of commutation failure(CF)of a line commutated converter based high-voltage direct current(LCC-HVDC)transmission,a DC chopper topology composed of power consumption sub-modules based on thyristor full-bridge module(TFB-PCSM)is proposed.Firstly,the mechanism of the proposed topology to mitigate CF is analyzed,and the working modes of TFB-PCSM in different operation states are introduced.Secondly,the coordinated control strategy between the proposed DC chopper and LCC-HVDC is designed,and the voltage-current stresses of the TFB-PCSMs are investigated.Finally,the ability to mitigate the CF issues and the fault recovery performance of LCC-HVDC system are studied in PSCAD/EMTDC.The results show that the probability of CF of LCC-HVDC is significantly reduced,and the performances of fault recovery are effectively improved by the proposed DC chopper.