Sewage source heat pump unit operates under partial load most of the time, and study on the law of coefficient of performance (COP) of the unit varying with load ratio can provide basis for the heat pump units running...Sewage source heat pump unit operates under partial load most of the time, and study on the law of coefficient of performance (COP) of the unit varying with load ratio can provide basis for the heat pump units running in high efficiency. A mathematical model determining COP, evaporation temperature and condensation temperature of a single unit was proposed. Under the condition of uniform load distribution, the model was established according to different ways of bearing partial load with the same type multi...展开更多
The flow and thermal breakthrough phenomenon in a forced external circulation standing column well(FECSCW)directly affects heat transfer efficiency and load-carrying capacity.A numerical model for FECSCW is developed ...The flow and thermal breakthrough phenomenon in a forced external circulation standing column well(FECSCW)directly affects heat transfer efficiency and load-carrying capacity.A numerical model for FECSCW is developed to analyze the migration of the temperature and velocity front under the flow and thermal breakthrough.The results indicated that thermal breakthrough began after simulation running 2.5 min and was completely formed after 12 min.The inlet water,which directly entered the production well without heat exchange with the aquifer,accounted for 12.8%.When the porosity of the backfill material decreased from 0.35 to 0,the coefficient of per-formance(COP)of the heat pump unit increased by 1.6%on average,and the thermal breakthrough strength decreased by an average of 45.3%within 25 min.Where seepage velocity near the well wall was greater than 1×10^(−3) m·s^(−1),faster velocity front migration was observed,while the migration advantage of the temperature front was more prominent outside of this region.Through quantitative analysis of flow and thermal breakthrough,temperature and velocity front migration,and COP change of heat pump unit,theoretical suggestions were pro-vided for the thermal transfer mechanism near the thermal well wall.The extended research in this study can be applied to the design and optimization of forced external circulation standing column well system.展开更多
基金Supported by National Natural Science Foundation of China (No. 50578048)"Heating, Gas, Ventilation and Air Conditioning" Key Laboratory Open Subject in Beijing (No. KF200710)the Postdoctoral Researcher Science Foundation of China (No. 20090450986)
文摘Sewage source heat pump unit operates under partial load most of the time, and study on the law of coefficient of performance (COP) of the unit varying with load ratio can provide basis for the heat pump units running in high efficiency. A mathematical model determining COP, evaporation temperature and condensation temperature of a single unit was proposed. Under the condition of uniform load distribution, the model was established according to different ways of bearing partial load with the same type multi...
基金This work was supported by the National Natural Science Foundation of China(41002085,41602278)China Postdoctoral Science Founda-tion(2016M601129)North China University of Technology Programs(18XN154-006,110052972027-031).
文摘The flow and thermal breakthrough phenomenon in a forced external circulation standing column well(FECSCW)directly affects heat transfer efficiency and load-carrying capacity.A numerical model for FECSCW is developed to analyze the migration of the temperature and velocity front under the flow and thermal breakthrough.The results indicated that thermal breakthrough began after simulation running 2.5 min and was completely formed after 12 min.The inlet water,which directly entered the production well without heat exchange with the aquifer,accounted for 12.8%.When the porosity of the backfill material decreased from 0.35 to 0,the coefficient of per-formance(COP)of the heat pump unit increased by 1.6%on average,and the thermal breakthrough strength decreased by an average of 45.3%within 25 min.Where seepage velocity near the well wall was greater than 1×10^(−3) m·s^(−1),faster velocity front migration was observed,while the migration advantage of the temperature front was more prominent outside of this region.Through quantitative analysis of flow and thermal breakthrough,temperature and velocity front migration,and COP change of heat pump unit,theoretical suggestions were pro-vided for the thermal transfer mechanism near the thermal well wall.The extended research in this study can be applied to the design and optimization of forced external circulation standing column well system.