This paper deals a detailed performance investigation of asymmetrical six-phase grid connected induction generator(GCIG)in two proposed configurations in variable speed operation.During the system development,regulati...This paper deals a detailed performance investigation of asymmetrical six-phase grid connected induction generator(GCIG)in two proposed configurations in variable speed operation.During the system development,regulation of DC-link voltage has been proposed using particle swarm optimization(PSO)based PI controller,ensuring the power flow to utility grid through back to back converters.The closed loop operation of asymmetrical six-phase GCIG using indirect field oriented control in different configurations has been carried out in Matlab/Simulink environment.Analytical results have been verified using real time test results on virtual platform of Typhoon HIL supported with some experimental validation.展开更多
文摘This paper deals a detailed performance investigation of asymmetrical six-phase grid connected induction generator(GCIG)in two proposed configurations in variable speed operation.During the system development,regulation of DC-link voltage has been proposed using particle swarm optimization(PSO)based PI controller,ensuring the power flow to utility grid through back to back converters.The closed loop operation of asymmetrical six-phase GCIG using indirect field oriented control in different configurations has been carried out in Matlab/Simulink environment.Analytical results have been verified using real time test results on virtual platform of Typhoon HIL supported with some experimental validation.