PCA weight and Johnson transformation based alarm threshold optimization in chemical processes 被引量:4
1
作者 Wende Tian Guixin Zhang +1 位作者 Xiang Zhang Yuxi Dong 《Chinese Journal of Chemical Engineering》 SCIE EI CAS CSCD 2018年第8期1653-1661,共9页
To alleviate the heavy load of massive alarm on operators, alarm threshold in chemical processes was optimized with principal component analysis(PCA) weight and Johnson transformation in this paper. First, few variabl... To alleviate the heavy load of massive alarm on operators, alarm threshold in chemical processes was optimized with principal component analysis(PCA) weight and Johnson transformation in this paper. First, few variables that have high PCA weight factors are chosen as key variables. Given a total alarm frequency to these variables initially, the allowed alarm number for each variable is determined according to their sampling time and weight factors. Their alarm threshold and then control limit percentage are determined successively. The control limit percentage of non-key variables is determined with 3σ method alternatively. Second, raw data are transformed into normal distribution data with Johnson function for all variables before updating their alarm thresholds via inverse transformation of obtained control limit percentage. Alarm thresholds are optimized by iterating this process until the calculated alarm frequency reaches standard level(normally one alarm per minute). Finally,variables and their alarm thresholds are visualized in parallel coordinate to depict their variation trends concisely and clearly. Case studies on a simulated industrial atmospheric-vacuum crude distillation demonstrate that the proposed alarm threshold optimization strategy can effectively reduce false alarm rate in chemical processes. 展开更多
关键词 Alarm threshold Chemical process PCA johnson transformation Variable weight
下载PDF
上一页 1 下一页 到第
使用帮助 返回顶部