A novel numerical algorithm of fault location estimation for double line to ground fault involving different phases from each of two parallel lines is presented in this paper.It is based on the one terminal voltag...A novel numerical algorithm of fault location estimation for double line to ground fault involving different phases from each of two parallel lines is presented in this paper.It is based on the one terminal voltage and current data.The loop and nodal equations comparing faulted phase with non faulted phase of two parallel lines are introduced in the fault location estimation models,in which the source impedance of a remote end is not involved.The effects of load flow and fault resistance on the accuracy of fault location are effectively eliminated,therefore precise algorithms of locating fault are derived.The algorithm is demonstrated by digital computer simulations.展开更多
基金Supported by Science Foundation of Guangdong(No.990 577)
文摘A novel numerical algorithm of fault location estimation for double line to ground fault involving different phases from each of two parallel lines is presented in this paper.It is based on the one terminal voltage and current data.The loop and nodal equations comparing faulted phase with non faulted phase of two parallel lines are introduced in the fault location estimation models,in which the source impedance of a remote end is not involved.The effects of load flow and fault resistance on the accuracy of fault location are effectively eliminated,therefore precise algorithms of locating fault are derived.The algorithm is demonstrated by digital computer simulations.